2017-08-31 16:29:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080651
 BRISTOL MECH SUBMITTALS
 8/31/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE UNIDENTIFIED PLAN SHEET THAT HAS BEEN "ATTACHED
 FOR REFERENCE" IN THE SUBMITTAL SHOWS ALTERATIONS TO
 THE FIRE/SMOKE AND FIRE DAMPER LOCATIONS. PLEASE
 INDICATE WHICH PLAN SHEETS, AND WHICH FLOORS OF THE
 BUILDING ARE AFFECTED BY THESE CHANGES BY SUBMITTING A
 NARRATIVE. CLARIFY IF THESE CHANGES ARE PART OF A
 REVISION THAT IS CURRENTLY IN FOR REVIEW, OR WILL BE IN
 FOR REVIEW AT A
  
 LATER DATE. PLEASE NOTE THAT ALL CHANGES TO THE
 APPROVED SMOKE CONTROL DESIGN MUST BE APPROVED BY THE
 DESIGN PROFESSIONALS OF RECORD, AND SLS WHO PREPARED
 THE SMOKE CONTROL RATIONAL ANALYSIS REPORT.
  