2017-12-20 16:45:572ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17080529
 12/20/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO COMMENT #2 FROM THE 1ST REVIEW, THE
 ARCHITECT IS STATING IN THE RESPONSE NARRATIVE THAT THE
 LAB ROOMS IN THE TENANT SPACE DO NOT HAVE TO MEET THE
 REQUIREMENTS OF TABLE 403.3. PLEASE SEE SECTION 403.3
 WHICH STATES: "VENTILATION RATES FOR OCCUPANCIES NOT
 REPRESENTED IN TABLE 403.3 SHALL BE THOSE FOR A LISTED
 OCCUPANCY CLASSIFICATION THAT IS MOST SIMILAR IN TERMS
  
 OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING
 CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED
 ENGINEERING ANALYSIS". ALTHOUGH LABS ARE NOT LISTED
 UNDER OFFICE OCCUPANCY, THEY ARE LISTED UNDER EDUCATION
 WHICH IS THE MOST SIMILAR OCCUPANCY SHOWN IN THE TABLE.
 PLEASE NOTE THAT THE EXISTENCE OF A LAB AS AN ACCESSORY
 SPACE IN A BUSINESS OCCUPANCY IS NOT PROHIBITED BY THE
 CODE-
  
 SEE SECTION 508 FBC-14 BUILDING. REVISE THE PLANS TO
 SHOW THE REQUIRED EXHAUST SYSTEMS, AND PROVIDE A
 NARRATIVE THAT DETAILS THE PROCEDURES THAT ARE
 PERFORMED IN THE LABS, AND WHAT EQUIPMENT AND MATERIALS
 ARE USED IN THOSE PROCEDURES. REFER TO TABLE 403.3 FOR
 LAB VENTILATION RATES- 10 CFM FOR OCCUPANTS PLUS 0.18
 CFMS PER SQ. FT. AND 1.0 CFM EXHAUST AIRFLOW RATE.
 PLEASE REVISE
  
 THE VENTILATION SCHEDULE ON SHEET MP001.
  
 2) IN RESPONSE TO COMMENT #5 FROM THE 1ST REVIEW
 CONCERNING THE RESTROOM AND GAS STORAGE ROOM EXHAUST,
 THE ARCHITECT IS STATING THAT THE GAS EXHAUST FAN
 (EF-2) IS DISCHARGING TO THE OUTDOORS, HOWEVER THE PLAN
 APPEARS TO STILL INDICATE THE EF-2 FAN ON THE INTERIOR
 WALL OF THE VESTIBULE. USING OUR GIS PROGRAM I HAVE
 LOOKED AT ACTUAL PHOTOS OF THE BUILDING AND I AM NOT
 SEEING HOW
  
 THE FAN LOCATED AS SHOWN ON THE PLAN IS ON AN EXTERIOR
 WALL. FURTHER, IF THIS FAN WAS LOCATED ON AN EXTERIOR
 WALL AT THE 6TH FLOOR LEVEL, HOW WOULD ACCESS BE
 PROVIDED TO SERVICE THE FAN AS REQUIRED BY CODE SECTION
 306.1. ADDITIONALLY PLEASE NOTE THE FAN WOULD HAVE TO
 BE WIND RESISTANT AND PROTECTED FROM IMPACT PER SECTION
 1609 FBC-14 BUILDING AND RULE 9N-3 FAC. CONCERNING
  
 THE LOCATION OF THE RESTOOM EXHAUST DISCHARGE, THE
 REVISED PLAN IS SHOWING AN 18"X 30" EXHAUST GRILL
 LOCATED IN A SOFFIT. AGAIN, I HAVE LOOKED AT THE PHOTOS
 AND NOT SEEING HOW THIS INSTALLATION WOULD BE
 ACCOMPLISHED. PLEASE PROVIDE PLAN SECTIONS AND DETAILS
 TO CLEARLY SHOW EACH OF THESE NEW EXHAUST TERMINATIONS.
  
 3) COMMENT #11 FROM THE 1ST REVIEW PARTIALLY COMPLIED
 WITH. AC CALCULATIONS FOR WSHP'S 7, 8, 9, 10, 11 NOT
 PROVIDED. PLEASE ADD THE EFFICIENCY RATINGS (SEER) TO
 THE EQUIPMENT SCHEDULE ON SHEET M001.
  
 4) SHEET M101: SHOW HOW O/A IS BEING PROVIDED TO THE
 WSHP-11 SYSTEM.
  
 5) M201: IT APPEARS THAT CONDENSATE FROM THE HEAT PUMPS
 WILL BE DRAINING INTO THE CITY SANITARY SYSTEM WHICH IS
 PROHIBITED PER SECTION 90-126 WPB CODE OF ORDINANCES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  