Date |
Text |
2017-12-12 14:10:10 | 400 SOUTH AUSTRALIAN AVENUE - 6TH FLOOR |
| PERMIT #17080529 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| REPEAT COMMENT - NO DRAWINGS SUBMITTED. ENGINEERED FIRE |
| SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A |
| GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS |
| BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE OF A GENERAL |
| BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA |
| BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA |
| ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| REPEAT COMMENT - NO DRAWINGS SUBMITTED. ENGINEERED FIRE |
| ALARM CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL |
| BUILDING PERMIT. PER FBC SECTION 907.1.1 CONSTRUCTION |
| DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM |
| SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL." |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| |