2017-12-27 07:52:53 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | PART VIII ELECTRICAL | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSES | | SATISFACTORILY EXCEPT NUMBER 3 SHOWN BELOW. THE PERMIT | | APPLICATION WAS SUBMITTED DURING THE TIME THAT THE 2014 | | FLORIDA BUILDING CODE IS IN EFFECT, WHICH REFERENCES | | THE 2011 NEC. PROVIDE CORRECTION TO SHOW THE DESIGN IS | | TO THE 2011 NEC. | | | | 3. NOTE 1 ON SHEET E-1 STATES ELECTRICAL INSTALLATION | | SHALL BE PER 2014 NEC, WHICH IS NOT THE CURRENT CODE. | | PROVIDE CORRECTION. AREAS COVERED BY NEC 517.13 SHOULD | | INCLUDE CONSULTATION AND OBSERVATION ROOMS. FBC | | PREFACE, NEC 517.13 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|