2017-12-27 07:52:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSES
 SATISFACTORILY EXCEPT NUMBER 3 SHOWN BELOW. THE PERMIT
 APPLICATION WAS SUBMITTED DURING THE TIME THAT THE 2014
 FLORIDA BUILDING CODE IS IN EFFECT, WHICH REFERENCES
 THE 2011 NEC. PROVIDE CORRECTION TO SHOW THE DESIGN IS
 TO THE 2011 NEC.
  
 3. NOTE 1 ON SHEET E-1 STATES ELECTRICAL INSTALLATION
 SHALL BE PER 2014 NEC, WHICH IS NOT THE CURRENT CODE.
 PROVIDE CORRECTION. AREAS COVERED BY NEC 517.13 SHOULD
 INCLUDE CONSULTATION AND OBSERVATION ROOMS. FBC
 PREFACE, NEC 517.13
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  