Plan Review Notes
Plan Review Notes For Permit 17080529
Permit Number 17080529
Review Stop P
Sequence Number 1
Notes
Date Text
2017-10-12 05:36:151) THE OCCUPANCY CLASSIFICATION OF BUSINESS ASSIGNED TO
 THE PROPOSED TENANT BUILD-OUT IS BEING QUESTIONED BY
 THE BUILDING AND FIRE DEPT. PLANS EXAMINERS. PLEASE
 NOTE THAT ADDITIONAL COMMENTS MAY OCCUR, OR
 COMMENTS MAY BE RETRACTED BASED ON THE DESIGN
 PROFESSIONALS CORRECTED PLANS AND RESPONSES.
 2) SHT. P301 - PROVIDE THE QUANTITY OF EACH CYLINDER OF
 EACH GAS AND THE CAPACITY OF EACH CYLINDER IN CUBIC
 FEET,
 3) INDICATE HOW THE MED GAS TANKS WILL BE SECURED AND
 PROTECTED FORM DAMAGE- SECTION 5.1.3.3.2 NFPA 99.
 4) SHOW LOCATIONS OF RELIEF VALVES AND RELIEF PIPING
 VENTS IN THE STORAGE ROOM AND WHERE THE VENT PIPING IS
 TERMINATING- NFPA 99 SECTION 5.1.3.3.3..
 5) PLEASE SUBMIT PRODUCT DATA SHEETS FOR ALL THE
 MEDICAL GAS SYSTEM EQUIPMENT, THE AIR COMPRESSOR, AND
 THE VACUUM PUMP WITH APPROVAL STAMPS BY THE EOR-
 SECTION 107.2.1 WPB AMENDMENTS.
 6) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 BOTTLED WATER DISPENSING STATION. THIS MAY HAVE TO
 COMPLY WITH THE 2014 FBC-ACCESSIBILITY CODE.
 7) THE ARCHITECT'S SEAL AND SIGNATURE ON THE DEMO AND
 ARCHITECTURAL PAGES APPEAR TO BE A COPY OF AN ORIGINAL
 SEAL AND SIGNATURE. COMPLY WITH F.A.C. 61G1-16.001.
 8) SUBMIT A PIPING RISER DIAGRAM FOR THE WATER PIPING
 SYSTEM(S) INCLUDING ANY WATER FILTRATION SYSTEM. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 9) SUBMIT A PIPING RISER DIAGRAM FOR THE ENTIRE MEDICAL
 GAS SYSTEM ( OXYGEN, NITROUS OXIDE) AND THE AIR AND
 VACUUM SYSTEM.WPB AMEND. TO FBC SEC. 107.3.5.1.3. THE
 MEDICAL GAS, AIR AND VACUUM SYSTEMS SHALL COMPLY WITH
 NFPA 99-12.
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE EMERGENCY EYE WASH UNITS.THE
 EYEWASH STATION SHALL COMPLY WITH 2014 FBC-PLUMBING
 SEC.411.1 AND ISEA Z358.1. TEMPERED WATER SHALL BE
 SUPPLIED TO THE EYEWASH. 2014 FBC-PLUMBING SEC.607.1.
 11) *** SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION MANUAL FOR THE AIR
 COMPRESSOR AND VACUUM PUMPS.THIS EQUIPMENT SHALL COMPLY
 WITH THE REQUIREMENTS OF NFPA 99, SECS.
 12) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE STERILIZATION CABINET. WPB
 AMEND. TO FBC SEC. 107.2.1.
 13) SHT.A3.9 - DETAIL # 2 - PROVIDE AN EXPANDED DETAIL
 OF THE VISTA CLEAR CABINET.THE DETAIL AND THE PRINT IS
 SMALL AND VERY HARD TO READ. WPB AMEND. TO FBC SEC.
 107.2.1.ALSO, SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THIS CABINET.
 14) PROVIDE TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS FOR THE DENTAL
 CHAIRS. WPB AMEND. TO FBC SEC. 107.2.1.
 15) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS & INSTALLATION MANUALS FOR ALL DENTAL
 EQUIPMENT THAT EMPLOYS A WATER OR DRAIN CONNECTION TO
 THE APPLIANCE/EQUIPMENT.WPB AMEND. TO FBC SEC. 107.2.1.
 16) SHT. A1.6 - CLARIFY THE ACRONYMNS "LDV" AND "HDV"
 ON THE VACUUM SYSTEM.
 17) SHT. A1.7 - SUBMIT A MINIMUM OF TWO COPIES OF THE
 MANUFACTURER'S PRE-INSTALLATION GUIDE FOR THE VACUUM
 PIPING SYSTEM TO BE PROVIDED BY A HENRY SCHEIN
 EQUIPMENT SALES SPECIALIST AS REFERENCED IN THE FIRST
 NOTE IN THE VACUUM SYSTEM NOTES ON THIS DRAWING PAGE.
 WPB AMEND. TO FBC SEC.107.2.1.
 18) SUBMIT TWO COPIES OF THE MEDICAL GAS SYSTEM
 DRAWINGS FROM HENRY SCHEIN.THESE DRAWINGS ARE REQUIRED
 TO BEAR THE SEAL AND SIGNATURE OF AN ENGINEER LICENSED
 IN THE STATE OF FLORIDA PER THE WPB AMEND. TO THE FBC
 SEC.105.3.1.2 (3), F.S. 471.
 19) SHT.A2.4 - DETAIL # 2 - THE SPACING OF THE GRAB BAR
 BEHIND THE WATER CLOSET SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SEC. 604.5.2.IF THE GRAB IS LOCATED A
 MAXIMUM OF ONE FOOT FROM THE SIDE WALL, THEN THERE WILL
 NOT BE THE REQUIRED MINIMUM OF 12 INCHES EXTENDING FROM
 THE CENTERLINE OF THE WATER CLOSET ON ONE SIDE. THE
 USUAL MAXIMUM DDISTANCE IS 6 INCHES. CLARIFY. SHOW THE
 RREQUIRED 12 INCHES AND 24 INCHES ON THE DETAIL.
 20) SHT. A3.3 - FIVE PERCENT OR A MINIMUM OF ONE OF THE
 SINKS IN THE DUAL USE ROOMS SHALL COMPLY WITH THE 2014
 FBC-ACCESSIBILITY SECS.212.3 & 606.
 21) SHT. A2.4 - DETAILS #3, #5 & #8 SHOW A VERTICAL
 GRAB BAR.ALTHOUGH THIS IS NOT A REQUIRED GRAB BAR, THE
 2014 FBC- ACCESSIBILITY SEC.609.4 REQUIRES GRAB BARS TO
 BE INSTALLED IN A HORIZONTAL POSITION. CLARIFY.
 22) SHT. A2.4 - DETAIL #4 - SHOW THE DIMENSIONS OF THE
 REQUIRED CLEAR FLOOR SPACES (LXW) FOR THE LAVATORY AND
 WATER CLOSET ON THE PLANS. COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS.604.3 & 606.2.
 24) STERILIZATION APPARTUS, WATER FILTERS, TANKS AND
 OTHER APPLIANCES THAT HANDLE OR TREAT POTABLE WATER
 SHALL BE PROTECTED AGAINST CONTAMINATION PER 2014
 FBC-PLUMBING SEC.608.3, 608.3.1. A BACKFLOW PREVENTER
 IS REQUIRED ON THESE TYPES OF EQUIPMENT.
 25) A BACKFLOW PREVENTER IS REQUIRED ON THE WATER
 SUPPLY AT THE BEVERAGE COUNTER AND ICE MAKER. 2014
 FBC-PLUMBING SEC.608.16.10.
 26) A WATER HAMMER ARRESTOR CONFORMING TO ASSE 1010
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED ON THE WATER DISTRIBUTION SYSTEM.2014
 FBC-PLUMBING SEC. 604.9.
 27) SHT. P001 - NOTE #16 REFERS TO SHT. A1.6 FOR A
 DETAIL OF A SEDIMENT TRAP. THERE IS NO DETAIL ON SHT.
 A1.6. CLARIFY.
 28) SHT. E-3 NOTES THE ELECTRIC WATER HEATER AS 30
 GALLONS AND SHT. P001 NOTES THE WATER HEATER AS 65
 GALLONS. CLARIFY.
 29) THE HOT WATER RECIRCULATION SYSTEM SHALL COMPLY
 WITH THE 2014 FBC-PLUMBING SEC.607.5 FOR THE REQUIRED
 PIPE INSULATION.
 30) SHT. P002 - BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED WWITH A VACUUM RELIEF VALVE PER 2014
 FBC-PLUMBING SEC. 504.2.
 31) SHT. P201 - NOTE #1 INDICATES A NEW 1 1/2 " COLD
 WATER CONNECTION TO AN EXISTING 1 1/4 " COLD WATER
 LINE. SUBMIT VERIFICATION THAT THE EXISTING 1 1/4"
 CCOLD WATER LINE WILL SUPPLY THE REQUIRED FLOW AND
 PRESSURES FOR THIS SYSTEM. 2014 FBC-PLUMBING
 SEC.604.3.**
 **NOTE** - ADDITIONAL REVIEW COMMENTS MAY BE GENERATED
 UPON RESUBMITTAL AND RE-REVIEW OF THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  