Plan Review Notes
Plan Review Notes For Permit 17080529
Permit Number 17080529
Review Stop M
Sequence Number 1
Notes
Date Text
2017-09-13 17:56:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080529
 9/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OCCUPANCY CLASSIFICATION OF BUSINESS ASSIGNED TO
 THE PROPOSED TENANT BUILD-OUT IS BEING QUESTIONED BY
 THE BUILDING AND FIRE DEPT. PLANS EXAMINERS. THE
 MECHANICAL PLANS AND SYSTEMS ARE BEING REVIEWED IN
 ACCORDANCE WITH THE FBC-14 MECHANICAL AND REFERENCED
 STANDARDS NFPA 99, AND ASHRAE 170- 2010. PLEASE NOTE
 THAT ADDITIONAL COMMENTS MAY OCCUR, OR
  
 COMMENTS MAY BE RETRACTED BASED ON THE DESIGN
 PROFESSIONALS CORRECTED PLANS AND RESPONSES.
  
 2) SHEET MP001: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE TECH LAB, DESIGN LAB, AND WET LAB
 IN COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL.
  
 3) MP001: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR THE DENTAL GAS STORAGE ROOM- SEE SECTION 502.9.1
 FBC-14 MECHANICAL. PLEASE NOTE THAT ADDITIONAL
 REQUIREMENTS FOR MEDICAL GAS EXHAUST SYSTEMS ARE FOUND
 IN SECTION 9.3.1.1 NFPA 99, AND SECTION 6 ASHRAE
 170-2010. PLEASE REFER TO SECTION 9.3.6.5.3.2 NFPA 99
 FOR EXHAUST VENTILATION RATE BASED ON THE QUANTITY OF
  
 GAS TO BE STORED.
  
 4) MP001: REFER TO TABLE 7-1 ASHRAE 170-2010 AND
 PROVIDE A DESIGN PARAMETER SCHEDULE ON THE PLAN FOR ALL
 ROOMS AND SPACES. THE SCHEDULE SHALL INDICATE PRESSURE
 RELATIONSHIPS TO ADJACENT AREAS, MINIMUM OUTDOOR ACH,
 TOTAL ACH ETC.
  
 5) M101: THE EXHAUST FROM EF-1 & EF-2 SHALL DISCHARGE
 TO THE EXTERIOR OF THE BUILDING PER SECTION 501.3
 FBC-14 MECHANICAL. IT APPEARS TO BE DISCHARGING INTO A
 STAIR VESTIBULE- SEE BUILDING AND FIRE COMMENTS.
  
 6) M101: IT APPEARS THAT MAKEUP AIR FOR THE EXHAUST IN
 THE STORAGE ROOM IS THROUGH A FIRE-DAMPERED OPENING
 INTO THE MECHANICAL ROOM. PLEASE SHOW COMPLIANCE WITH
 SECTIONS 5.1.3.3.1.5 NFPA 99 FOR ADJACENT ROOM
 COMMUNICATION RESTRICTIONS, AND 9.3.6.5.3.7 FOR MAKEUP
 AIR REQUIRERMENTS.
  
 7) M101: PROVIDE AN EQUIPMENT SCHEDULE FOR THE FIRE
 DAMPER AND A SEQUENCE OF OPERATION. CLARIFY HOW WILL
 THIS DAMPER FUNCTION IN AN ALARM SITUATION.
  
 8) INDICATE THE TOTAL QUANTITIES OF NITROUS OXIDE AND
 OXYGEN TO BE STORED IN THE ROOM- SECTION 5.1.3.3.1.7
 NFPA 99. REFER TO SECTION 502.9.1 FBC-14 MECHANICAL:
 THE EXHAUST VENT FOR THE STORAGE ROOM MAY BE REQUIRED
 TO BE ENCLOSED IN A MINIMUM 1HR FIRE-RATED SHAFT
 ENCLOSURE FROM THE STORAGE ROOM TO THE EXTERIOR. NOTE 3
 ON SHEET M101 INDICATES THE DUCT IS TO BE WRAPPED WITH
  
 3M FIRE BARRIER WRAP. THE SPECIFICATIONS FOR THE FIRE
 WRAP MUST SHOW COMPATIBILTY FOR THIS TYPE OF SYSTEM
 APPLICATION, AND BE SUBMITTED FOR REVIEW WITH APPROVAL
 STAMPS BY THE ENGINEER OF RECORD.
  
 9) INDICATE HOW THE MED GAS TANKS WILL BE SECURED AND
 PROTECTED FORM DAMAGE- SECTION 5.1.3.3.2 NFPA 99.
  
 10) SHOW LOCATIONS OF RELIEF VALVES AND RELIEF PIPING
 VENTS IN THE STORAGE ROOM AND WHERE THE VENT PIPING IS
 TERMINATING- SECTION 5.1.3.3.3.2.
  
 11) PLEASE SUBMIT PRODUCT DATA SHEETS FOR ALL THE MED
 GAS SYSTEM EQUIPMENT, THE COMPRESSOR, AND THE VACUUM
 WITH APPROVAL STAMPS BY THE EOR- SECTION 107.2.1 WPB
 AMENDMENTS.
  
 12) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE
 NEW WSHP SYSTEMS- SECTION 312.1. FBC-14 MECHANICAL.
  
 13) M101: A SMOKE DETECTOR IS REQUIRED IN THE
 MECHANICAL ROOM IN COMPLIANCE WITH SECTION 606.2.2
 FBC-14 MECHANICAL.
  
 14) M101: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.4
 FBC-14 ENERGY CONSERVATION.
  
 15) PROVIDE AIR BALANCE CALCULATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  