2017-09-13 17:56:49 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17080529 |
| 9/13/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE OCCUPANCY CLASSIFICATION OF BUSINESS ASSIGNED TO |
| THE PROPOSED TENANT BUILD-OUT IS BEING QUESTIONED BY |
| THE BUILDING AND FIRE DEPT. PLANS EXAMINERS. THE |
| MECHANICAL PLANS AND SYSTEMS ARE BEING REVIEWED IN |
| ACCORDANCE WITH THE FBC-14 MECHANICAL AND REFERENCED |
| STANDARDS NFPA 99, AND ASHRAE 170- 2010. PLEASE NOTE |
| THAT ADDITIONAL COMMENTS MAY OCCUR, OR |
| |
| COMMENTS MAY BE RETRACTED BASED ON THE DESIGN |
| PROFESSIONALS CORRECTED PLANS AND RESPONSES. |
| |
| 2) SHEET MP001: PROVIDE EXHAUST VENTILATION |
| CALCULATIONS FOR THE TECH LAB, DESIGN LAB, AND WET LAB |
| IN COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL. |
| |
| 3) MP001: PROVIDE AN EXHAUST VENTILATION CALCULATION |
| FOR THE DENTAL GAS STORAGE ROOM- SEE SECTION 502.9.1 |
| FBC-14 MECHANICAL. PLEASE NOTE THAT ADDITIONAL |
| REQUIREMENTS FOR MEDICAL GAS EXHAUST SYSTEMS ARE FOUND |
| IN SECTION 9.3.1.1 NFPA 99, AND SECTION 6 ASHRAE |
| 170-2010. PLEASE REFER TO SECTION 9.3.6.5.3.2 NFPA 99 |
| FOR EXHAUST VENTILATION RATE BASED ON THE QUANTITY OF |
| |
| GAS TO BE STORED. |
| |
| 4) MP001: REFER TO TABLE 7-1 ASHRAE 170-2010 AND |
| PROVIDE A DESIGN PARAMETER SCHEDULE ON THE PLAN FOR ALL |
| ROOMS AND SPACES. THE SCHEDULE SHALL INDICATE PRESSURE |
| RELATIONSHIPS TO ADJACENT AREAS, MINIMUM OUTDOOR ACH, |
| TOTAL ACH ETC. |
| |
| 5) M101: THE EXHAUST FROM EF-1 & EF-2 SHALL DISCHARGE |
| TO THE EXTERIOR OF THE BUILDING PER SECTION 501.3 |
| FBC-14 MECHANICAL. IT APPEARS TO BE DISCHARGING INTO A |
| STAIR VESTIBULE- SEE BUILDING AND FIRE COMMENTS. |
| |
| 6) M101: IT APPEARS THAT MAKEUP AIR FOR THE EXHAUST IN |
| THE STORAGE ROOM IS THROUGH A FIRE-DAMPERED OPENING |
| INTO THE MECHANICAL ROOM. PLEASE SHOW COMPLIANCE WITH |
| SECTIONS 5.1.3.3.1.5 NFPA 99 FOR ADJACENT ROOM |
| COMMUNICATION RESTRICTIONS, AND 9.3.6.5.3.7 FOR MAKEUP |
| AIR REQUIRERMENTS. |
| |
| 7) M101: PROVIDE AN EQUIPMENT SCHEDULE FOR THE FIRE |
| DAMPER AND A SEQUENCE OF OPERATION. CLARIFY HOW WILL |
| THIS DAMPER FUNCTION IN AN ALARM SITUATION. |
| |
| 8) INDICATE THE TOTAL QUANTITIES OF NITROUS OXIDE AND |
| OXYGEN TO BE STORED IN THE ROOM- SECTION 5.1.3.3.1.7 |
| NFPA 99. REFER TO SECTION 502.9.1 FBC-14 MECHANICAL: |
| THE EXHAUST VENT FOR THE STORAGE ROOM MAY BE REQUIRED |
| TO BE ENCLOSED IN A MINIMUM 1HR FIRE-RATED SHAFT |
| ENCLOSURE FROM THE STORAGE ROOM TO THE EXTERIOR. NOTE 3 |
| ON SHEET M101 INDICATES THE DUCT IS TO BE WRAPPED WITH |
| |
| 3M FIRE BARRIER WRAP. THE SPECIFICATIONS FOR THE FIRE |
| WRAP MUST SHOW COMPATIBILTY FOR THIS TYPE OF SYSTEM |
| APPLICATION, AND BE SUBMITTED FOR REVIEW WITH APPROVAL |
| STAMPS BY THE ENGINEER OF RECORD. |
| |
| 9) INDICATE HOW THE MED GAS TANKS WILL BE SECURED AND |
| PROTECTED FORM DAMAGE- SECTION 5.1.3.3.2 NFPA 99. |
| |
| 10) SHOW LOCATIONS OF RELIEF VALVES AND RELIEF PIPING |
| VENTS IN THE STORAGE ROOM AND WHERE THE VENT PIPING IS |
| TERMINATING- SECTION 5.1.3.3.3.2. |
| |
| 11) PLEASE SUBMIT PRODUCT DATA SHEETS FOR ALL THE MED |
| GAS SYSTEM EQUIPMENT, THE COMPRESSOR, AND THE VACUUM |
| WITH APPROVAL STAMPS BY THE EOR- SECTION 107.2.1 WPB |
| AMENDMENTS. |
| |
| 12) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE |
| NEW WSHP SYSTEMS- SECTION 312.1. FBC-14 MECHANICAL. |
| |
| 13) M101: A SMOKE DETECTOR IS REQUIRED IN THE |
| MECHANICAL ROOM IN COMPLIANCE WITH SECTION 606.2.2 |
| FBC-14 MECHANICAL. |
| |
| 14) M101: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF |
| DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.4 |
| FBC-14 ENERGY CONSERVATION. |
| |
| 15) PROVIDE AIR BALANCE CALCULATIONS. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |