2017-09-13 11:21:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10
 2. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS,
 HOODS, ETC. FBC 105.1
 3. NOTE 1 ON SHEET E-1 STATES ELECTRICAL INSTALLATION
 SHALL BE PER 2014 NEC, WHICH IS NOT THE CURRENT CODE.
 PROVIDE CORRECTION. AREAS COVERED BY NEC 517.13 SHOULD
 INCLUDE CONSULTATION AND OBSERVATION ROOMS. FBC
 PREFACE, NEC 517.13
 4. NOTE 4 ON SHEET E-1 STATES THAT ISOLATED GROUND
 RECEPTACLES SHOULD BE USED. NEC 517.16 PROHIBITS THE
 USE OF IG RECEPTACLES. PROVIDE CORRECTION. NEC 517.16
 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1. CODE REQUIRES CONTROL AS
 FOLLOWS: AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP
 RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS,
 ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING
 FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL
 WORKSTATIONS.
 6. IF OCCUPANCY IS CLASSIFIED AS AMBULATORY CARE
 FACILITY PER THE BUILDING COMMENTS, PROVIDE ALTERNATE
 POWER SOURCE REQUIRED. NEC 517.45
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  