2017-09-13 11:21:39 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS |
| ADEQUATE. NEC 110.10 |
| 2. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV, |
| PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS, |
| HOODS, ETC. FBC 105.1 |
| 3. NOTE 1 ON SHEET E-1 STATES ELECTRICAL INSTALLATION |
| SHALL BE PER 2014 NEC, WHICH IS NOT THE CURRENT CODE. |
| PROVIDE CORRECTION. AREAS COVERED BY NEC 517.13 SHOULD |
| INCLUDE CONSULTATION AND OBSERVATION ROOMS. FBC |
| PREFACE, NEC 517.13 |
| 4. NOTE 4 ON SHEET E-1 STATES THAT ISOLATED GROUND |
| RECEPTACLES SHOULD BE USED. NEC 517.16 PROHIBITS THE |
| USE OF IG RECEPTACLES. PROVIDE CORRECTION. NEC 517.16 |
| 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| 8.4.2. FBC CE 405.7.1. CODE REQUIRES CONTROL AS |
| FOLLOWS: AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP |
| RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS, |
| ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING |
| FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL |
| WORKSTATIONS. |
| 6. IF OCCUPANCY IS CLASSIFIED AS AMBULATORY CARE |
| FACILITY PER THE BUILDING COMMENTS, PROVIDE ALTERNATE |
| POWER SOURCE REQUIRED. NEC 517.45 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |