Date |
Text |
2017-08-24 14:30:39 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17080529 |
| ADD: 400 S AUSTRALIAN AVE. / SUITE: 6TH FLOOR |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 954-914-9848 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. AUGUST 10/ 2017 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET STATES THAT THE OCCUPANCY IS A |
| BUSINESS OCCUPANCY, AND GOES FURTHER UNDER THE USE |
| DISCLOSURE STATEMENT THAT SEDATED PATIENTS ARE NOT |
| RENDERED UNCONSCIOUS. IN VIEWING THE MSDS SHEETS FOR |
| NITROUS OXIDE- INHALATION. MAY CAUSE EXCITATION, |
| DIZZINESS, DROWSINESS, POOR COORDINATION, AND NARCOSIS |
| ( NARCOSIS PRODUCES A STATE SIMILAR TO DRUNKENNESS). |
| |
| THE P03 SHEET SHOWS 9 CUBICLES THAT HAVE BOTH OXYGEN |
| AND NITROUS OXIDE PIPED INTO EACH UNIT. THE 2014 FBC-B |
| MAKES THE DISTENSION BETWEEN A BUSINESS OCCUPANCY AND |
| AMBULATORY CARE FACILITY WHEN THERE IS A POTENTIAL FOR |
| FOUR OR MORE CARE RECIPIENTS ARE TO BE INCAPABLE OF |
| SELF-PRESERVATION AT ANY TIME, WHETHER RENDERED |
| INCAPABLE BY STAFF OR STAFF ACCEPTED RESPONSIBILITY FOR |
| A CARE RECIPIENT ALREADY INCAPABLE, THIS MAKES THE |
| TENANT SPACE A AMBULATORY CARE FACILITY. COVERED UNDER |
| THE 2014 FBC-B 422.1- 422.7. |
| |
| 1A) 422.2 SEPARATION. AMBULATORY CARE FACILITIES WHERE |
| THE POTENTIAL FOR FOUR OR MORE CARE RECIPIENTS ARE TO |
| BE INCAPABLE OF SELF-PRESERVATION AT ANY TIME, WHETHER |
| RENDERED INCAPABLE BY STAFF OR STAFF ACCEPTED |
| RESPONSIBILITY FOR A CARE RECIPIENT ALREADY INCAPABLE, |
| SHALL BE SEPARATED FROM ADJACENT SPACES, CORRIDORS OR |
| TENANTS WITH A FIRE PARTITION INSTALLED IN ACCORDANCE |
| WITH SECTION 708. |
| |
| 1B) 422.3 SMOKE COMPARTMENTS. NOT APPLICABLE, THE |
| FACILITY IS NOT LARGER THAN 10,000 SQ. FT. |
| |
| 1C) SHOW COMPLIANCE. 422.4 REFUGE AREA. NOT LESS THAN |
| 30 NET SQUARE FEET (2.8 M2) FOR EACH NONAMBULATORY CARE |
| RECIPIENT SHALL BE PROVIDED WITHIN THE AGGREGATE AREA |
| OF CORRIDORS, CARE RECIPIENT ROOMS, TREATMENT ROOMS, |
| LOUNGE OR DINING AREAS AND OTHER LOW-HAZARD AREAS |
| WITHIN EACH SMOKE COMPARTMENT. EACH OCCUPANT OF AN |
| AMBULATORY CARE FACILITY SHALL BE PROVIDED WITH ACCESS |
| TO A REFUGE AREA WITHOUT PASSING THROUGH OR UTILIZING |
| ADJACENT TENANT SPACES. |
| |
| 1D) 422.5 INDEPENDENT EGRESS. NOT APPLICABLE. |
| |
| 1E) SHOW COMPLIANCE. FBC-B 422.6 AUTOMATIC SPRINKLER |
| SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED |
| FOR AMBULATORY CARE FACILITIES IN ACCORDANCE WITH |
| SECTION 903.2.2. |
| FBC-B 903.2.2 AMBULATORY CARE FACILITIES. AN AUTOMATIC |
| SPRINKLER SYSTEM SHALL BE INSTALLED THROUGHOUT THE |
| ENTIRE FLOOR CONTAINING AN AMBULATORY CARE FACILITY |
| WHERE EITHER OF THE FOLLOWING CONDITIONS EXIST AT ANY |
| TIME: |
| 1. FOUR OR MORE CARE RECIPIENTS ARE INCAPABLE OF |
| SELF-PRESERVATION, WHETHER RENDERED INCAPABLE BY STAFF |
| OR STAFF HAS ACCEPTED RESPONSIBILITY FOR CARE |
| RECIPIENTS ALREADY INCAPABLE. |
| 2. ONE OR MORE CARE RECIPIENTS THAT ARE INCAPABLE OF |
| SELF-PRESERVATION ARE LOCATED AT OTHER THAN THE LEVEL |
| OF EXIT DISCHARGE SERVING SUCH A FACILITY. |
| |
| 1F) SHOW COMPLIANCE. FBC-B 422.7 FIRE ALARM SYSTEMS. A |
| FIRE ALARM SYSTEM SHALL BE PROVIDED FOR AMBULATORY CARE |
| FACILITIES IN ACCORDANCE WITH SECTION 907.2.2. |
| |
| 2) THE COVERSHEET INDICATES THE FIRE SPRINKLERS ARE |
| GOING TO BE A DESIGN BUILD SYSTEM. PLEASE NOTE THE |
| FBC-B UNDER SECTIONS 422.6 AND 903.2.2 BOTH REQUIRE |
| FIRE SPRINKLER PLANS BEFORE PERMIT ISSUANCE. THE SAME |
| IS REQUIRED FOR FIRE ALARM. BOTH FIRE SPRINKLER AND |
| FIRE ALARM REQUIRE A SEPARATE PERMIT. |
| |
| 3) SHEET A103 SHOWS THE ROOM 641 TO BE A 1 HOUR FIRE |
| RATED ROOM WHICH CONTAINS THE VARIOUS BOTTLED GASSES. |
| PLEASE PROVIDE THE MSDS SHEETS FOR NITROUS OXIDE & |
| OXYGEN. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 4) P301 SHOW THERE TO BE 4 CYLINDERS WITHIN THE ROOM. |
| P003 INDICATES NITROUS OXIDE, OXYGEN AND AIR. PLEASE |
| PROVIDE THE QUANTITY OF CYLINDERS OF EACH GAS, SIZE OF |
| CYLINDER IN CUBIC FEET TO SEE IF THE QUANTITIES OF GAS |
| MEET THE REQUIREMENTS FOR CONTROL AREAS UNDER FBC-B |
| TABLE 307.1(1). |
| |
| 5) DATE 9/14/17 IN DISCUSSING THE MECHANICAL SHEET M101 |
| WITH OUR MECHANICAL REVIEWER CHRIS COLE, THIS SHEET |
| SHOWS EXHAUST AIR BEING BROUGHT INTO THE 2 HOUR RATED |
| STAIR VESSTIBULE. THE REQUIREMENT FOR SMOKEPROOF |
| ENCLOSURES IS FOUND IN FBC-B 1022.10. THIS ALSO BRINGS |
| US TO 909.20 SMOKEPROOF ENCLOSUES AND |
| 909.20.2VCONSTRUCTION. THERE IS A QUESTION OF WHICH |
| CODE REQUIREMENTS ARE BEING MET 909.20.3.3. VESTIBULE |
| VENTILATION OR 909.20.4 MECHANICAL VENTILATION |
| ALTERNATIVE. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |