Plan Review Notes
Plan Review Notes For Permit 17080529
Permit Number 17080529
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-24 14:30:392014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080529
 ADD: 400 S AUSTRALIAN AVE. / SUITE: 6TH FLOOR
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-914-9848
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 10/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET STATES THAT THE OCCUPANCY IS A
 BUSINESS OCCUPANCY, AND GOES FURTHER UNDER THE USE
 DISCLOSURE STATEMENT THAT SEDATED PATIENTS ARE NOT
 RENDERED UNCONSCIOUS. IN VIEWING THE MSDS SHEETS FOR
 NITROUS OXIDE- INHALATION. MAY CAUSE EXCITATION,
 DIZZINESS, DROWSINESS, POOR COORDINATION, AND NARCOSIS
 ( NARCOSIS PRODUCES A STATE SIMILAR TO DRUNKENNESS).
  
 THE P03 SHEET SHOWS 9 CUBICLES THAT HAVE BOTH OXYGEN
 AND NITROUS OXIDE PIPED INTO EACH UNIT. THE 2014 FBC-B
 MAKES THE DISTENSION BETWEEN A BUSINESS OCCUPANCY AND
 AMBULATORY CARE FACILITY WHEN THERE IS A POTENTIAL FOR
 FOUR OR MORE CARE RECIPIENTS ARE TO BE INCAPABLE OF
 SELF-PRESERVATION AT ANY TIME, WHETHER RENDERED
 INCAPABLE BY STAFF OR STAFF ACCEPTED RESPONSIBILITY FOR
 A CARE RECIPIENT ALREADY INCAPABLE, THIS MAKES THE
 TENANT SPACE A AMBULATORY CARE FACILITY. COVERED UNDER
 THE 2014 FBC-B 422.1- 422.7.
  
 1A) 422.2 SEPARATION. AMBULATORY CARE FACILITIES WHERE
 THE POTENTIAL FOR FOUR OR MORE CARE RECIPIENTS ARE TO
 BE INCAPABLE OF SELF-PRESERVATION AT ANY TIME, WHETHER
 RENDERED INCAPABLE BY STAFF OR STAFF ACCEPTED
 RESPONSIBILITY FOR A CARE RECIPIENT ALREADY INCAPABLE,
 SHALL BE SEPARATED FROM ADJACENT SPACES, CORRIDORS OR
 TENANTS WITH A FIRE PARTITION INSTALLED IN ACCORDANCE
 WITH SECTION 708.
  
 1B) 422.3 SMOKE COMPARTMENTS. NOT APPLICABLE, THE
 FACILITY IS NOT LARGER THAN 10,000 SQ. FT.
  
 1C) SHOW COMPLIANCE. 422.4 REFUGE AREA. NOT LESS THAN
 30 NET SQUARE FEET (2.8 M2) FOR EACH NONAMBULATORY CARE
 RECIPIENT SHALL BE PROVIDED WITHIN THE AGGREGATE AREA
 OF CORRIDORS, CARE RECIPIENT ROOMS, TREATMENT ROOMS,
 LOUNGE OR DINING AREAS AND OTHER LOW-HAZARD AREAS
 WITHIN EACH SMOKE COMPARTMENT. EACH OCCUPANT OF AN
 AMBULATORY CARE FACILITY SHALL BE PROVIDED WITH ACCESS
 TO A REFUGE AREA WITHOUT PASSING THROUGH OR UTILIZING
 ADJACENT TENANT SPACES.
  
 1D) 422.5 INDEPENDENT EGRESS. NOT APPLICABLE.
  
 1E) SHOW COMPLIANCE. FBC-B 422.6 AUTOMATIC SPRINKLER
 SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED
 FOR AMBULATORY CARE FACILITIES IN ACCORDANCE WITH
 SECTION 903.2.2.
 FBC-B 903.2.2 AMBULATORY CARE FACILITIES. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE INSTALLED THROUGHOUT THE
 ENTIRE FLOOR CONTAINING AN AMBULATORY CARE FACILITY
 WHERE EITHER OF THE FOLLOWING CONDITIONS EXIST AT ANY
 TIME:
 1. FOUR OR MORE CARE RECIPIENTS ARE INCAPABLE OF
 SELF-PRESERVATION, WHETHER RENDERED INCAPABLE BY STAFF
 OR STAFF HAS ACCEPTED RESPONSIBILITY FOR CARE
 RECIPIENTS ALREADY INCAPABLE.
 2. ONE OR MORE CARE RECIPIENTS THAT ARE INCAPABLE OF
 SELF-PRESERVATION ARE LOCATED AT OTHER THAN THE LEVEL
 OF EXIT DISCHARGE SERVING SUCH A FACILITY.
  
 1F) SHOW COMPLIANCE. FBC-B 422.7 FIRE ALARM SYSTEMS. A
 FIRE ALARM SYSTEM SHALL BE PROVIDED FOR AMBULATORY CARE
 FACILITIES IN ACCORDANCE WITH SECTION 907.2.2.
  
 2) THE COVERSHEET INDICATES THE FIRE SPRINKLERS ARE
 GOING TO BE A DESIGN BUILD SYSTEM. PLEASE NOTE THE
 FBC-B UNDER SECTIONS 422.6 AND 903.2.2 BOTH REQUIRE
 FIRE SPRINKLER PLANS BEFORE PERMIT ISSUANCE. THE SAME
 IS REQUIRED FOR FIRE ALARM. BOTH FIRE SPRINKLER AND
 FIRE ALARM REQUIRE A SEPARATE PERMIT.
  
 3) SHEET A103 SHOWS THE ROOM 641 TO BE A 1 HOUR FIRE
 RATED ROOM WHICH CONTAINS THE VARIOUS BOTTLED GASSES.
 PLEASE PROVIDE THE MSDS SHEETS FOR NITROUS OXIDE &
 OXYGEN. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) P301 SHOW THERE TO BE 4 CYLINDERS WITHIN THE ROOM.
 P003 INDICATES NITROUS OXIDE, OXYGEN AND AIR. PLEASE
 PROVIDE THE QUANTITY OF CYLINDERS OF EACH GAS, SIZE OF
 CYLINDER IN CUBIC FEET TO SEE IF THE QUANTITIES OF GAS
 MEET THE REQUIREMENTS FOR CONTROL AREAS UNDER FBC-B
 TABLE 307.1(1).
  
 5) DATE 9/14/17 IN DISCUSSING THE MECHANICAL SHEET M101
 WITH OUR MECHANICAL REVIEWER CHRIS COLE, THIS SHEET
 SHOWS EXHAUST AIR BEING BROUGHT INTO THE 2 HOUR RATED
 STAIR VESSTIBULE. THE REQUIREMENT FOR SMOKEPROOF
 ENCLOSURES IS FOUND IN FBC-B 1022.10. THIS ALSO BRINGS
 US TO 909.20 SMOKEPROOF ENCLOSUES AND
 909.20.2VCONSTRUCTION. THERE IS A QUESTION OF WHICH
 CODE REQUIREMENTS ARE BEING MET 909.20.3.3. VESTIBULE
 VENTILATION OR 909.20.4 MECHANICAL VENTILATION
 ALTERNATIVE.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved