Plan Review Notes For Permit 17080504 |
Permit Number |
17080504 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-11 06:26:19 | 1) SUBMIT A PERMIT APPLICATION FROM A PLUMBING | | CONTRACTOR. A GENERAL CONTRACTOR CANNOT PERFORM THIS | | WORK AS IT DOES NOT FALL UNDER THE SCOPE OF HIS LICENSE | | PER FL. STATUTE 489.105. | | 2) SPECIFICATIONS FOR A DOUBLE DETECTOR CHECK VALVE | | HAVE BEEN SUBMITTED FOR THIS INSTALLATION. THE DOUBLE | | DETECTOR CHECK VALVE IS NOT WHAT IS INSTALLED ONSITE. A | | REDUCED PRESSURE ZONE VALVE HAS BEEN INSTALLED. SUBMIT | | TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR THE | | BACKFLOW DEVICE THAT HAS BEEN INSTALLED.WPB AMEND. TO | | FBC SEC. 107.2.1. | | 3) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR | | THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE | | DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK | | SECTION ON THE PERMIT APPLICATION. | | 4) ALL BACKFLOW DEVICES MUST BE LEAD FREE. | | 5) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF | | SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|