Plan Review Notes
Plan Review Notes For Permit 17080504
Permit Number 17080504
Review Stop P
Sequence Number 1
Notes
Date Text
2017-08-11 06:26:191) SUBMIT A PERMIT APPLICATION FROM A PLUMBING
 CONTRACTOR. A GENERAL CONTRACTOR CANNOT PERFORM THIS
 WORK AS IT DOES NOT FALL UNDER THE SCOPE OF HIS LICENSE
 PER FL. STATUTE 489.105.
 2) SPECIFICATIONS FOR A DOUBLE DETECTOR CHECK VALVE
 HAVE BEEN SUBMITTED FOR THIS INSTALLATION. THE DOUBLE
 DETECTOR CHECK VALVE IS NOT WHAT IS INSTALLED ONSITE. A
 REDUCED PRESSURE ZONE VALVE HAS BEEN INSTALLED. SUBMIT
 TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR THE
 BACKFLOW DEVICE THAT HAS BEEN INSTALLED.WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE
 DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
 4) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
 5) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW