Plan Review Notes
Plan Review Notes For Permit 17080496
Permit Number 17080496
Review Stop P
Sequence Number 1
Notes
Date Text
2018-01-25 06:43:401) SUBMIT A COPY OF THE OPERATING PERMIT APPLICATION
 FROM THE DEPARTMENT OF HEALTH FOR THE POOL IN
 ACCORDANCE WITH FL. STATUTES 514.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN COVERS. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 POOL HEATERS. THE GAS HEATERS SHALL MEET THE
 REQUIREMENTS OF THE 2014 FBC-ENERGY SEC. C404.7.1 &
 TABLE C404.2.
 4) CP4.0 - SHOW THE DISTANCE FROM FINISH SLAB/DECK TO
 THE HEIGHT OF THE POOL CHAIN LEVER FOR THE SHOWER.THE
 MAXIMUM HEIGHT OF THE PULL LEVER MAY HAVE TO COMPLY
 WITH THE FAC.MAX. HEIGHT WOULD BE 48 INCHES ABOVE
 FINISH SLAB/DECK.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  