2017-12-27 11:06:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THIS APPLICATION IS FOR THE POOL, HOWEVER, I DO NOT
 SEE ELECTRICAL PLANS FOR THE POOL OR POOL EQUIPMENT.
 THE PLAN PROVIDED APPEARS TO BE REVISIONS TO THE
 DIFFERENT LEVELS, WHICH SHOULD BE SUBMITTED AS A
 REVISION. PROVIDE POOL ELECTRICAL PLAN FOR REVIEW,
 SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN. FS
 481.229; FBC 107.2.1, 107.3.5
 2. NO VALUE IS LISTED ON PERMIT APPLICATION. THE VALUE
 OF A POOL IS NOT INCLUDED IN THE MASTER PERMIT. PROVIDE
 COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK,
 TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  