2017-12-27 11:06:28 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THIS APPLICATION IS FOR THE POOL, HOWEVER, I DO NOT |
| SEE ELECTRICAL PLANS FOR THE POOL OR POOL EQUIPMENT. |
| THE PLAN PROVIDED APPEARS TO BE REVISIONS TO THE |
| DIFFERENT LEVELS, WHICH SHOULD BE SUBMITTED AS A |
| REVISION. PROVIDE POOL ELECTRICAL PLAN FOR REVIEW, |
| SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN. FS |
| 481.229; FBC 107.2.1, 107.3.5 |
| 2. NO VALUE IS LISTED ON PERMIT APPLICATION. THE VALUE |
| OF A POOL IS NOT INCLUDED IN THE MASTER PERMIT. PROVIDE |
| COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK, |
| TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |