2017-08-25 12:10:42 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MP |
| REGULATORS.NOTHING HAS BEEN SUBMITTED. 2ND REQUEST. |
| 2) SHOW THE DISTANCE FROM EACH MP REGULATOR TO THE MOST |
| REMOTE OUTLET IN THE BRANCH LINE PER THE 2014FBC-FUEL |
| GAS SEC. 402.4.1, 2014 FBCR SEC. G 2413.3. THIS IS FOR |
| THE LOW PRESSURE SIDE OF EACH MP REGULATOR.2ND REQUEST. |
| 3) SUBMIT THE CORRECT CORRESPONDING EHD NUMBER FOR THE |
| CSST PIPE SIZES. THERE ARE INCORRECT EHD SIZES NOTED ON |
| THE GAS RISER FOR THE CORRESPONDING PIPE SIZES.. COMPLY |
| WITH THE SIZING TABLE(S) IN THE 2014 FBC-FUEL GAS OR |
| THE WARDFLEX GAS SIZING TABLE.SUBMIT TWO COPIES OF THE |
| WARDFLEX PIPE SIZING TABLE FOR REVIEW FOR THE SIZING OF |
| THE CSST. WPB AMEND. TO FBC SEC. 107.3.5.3. 2ND REQUEST |
| 4) I HAVE ADDED THE TOTAL BTU LOAD SEVERAL TIMES AND I |
| HAVE CALCULATED 2,229,000 BTU'S. PLEASE CHECK YOUR BTU |
| AND REVISE. |
| 5) THE GAS RISER SHOWS A 1/2 INCH GALVANIZED NEAR THE |
| GAS RANGE SUPPLYING A 1 INCH CSST LINE THAT SUPPLIES |
| TWO FIREPLACES. IS THIS CORRECT? THE 1/2 INCH |
| GALVANIZED LINE IS UNDERSIZED. CLARIFY. |
| 6) SHOW THE TYPE OF PIPING AND LENGTH FOR THE 1/2 INCH |
| DROP TO THE BBQ AND ALSO THE 3/4 INCH RISER TO THE BBQ. |
| 7) THE 3/4 CSST BRANCH LINE SUPPLYING THE FIREPLACE IN |
| THE FIRST FLOOR LOGGIA AND THE SECOND FLOOR MASTER |
| TERRACE IS UNDERSIZED.COMPLY WITH 2014 FBC-FUEL GAS |
| CHAPTER 4. |
| 8) SHOW THE LENGTH OF SECTION OF PIPING FOR ALL RISERS |
| TO THE 2ND FLOOR. WPB AMEND. TO FBC SEC. 107.3.5.3. |
| 9) SHT. P103 NOTE ON PLANS REFERS TO THE GAS REGULATORS |
| BEING EQUIPPED WITH A LEAK LIMITING DEVICE. VENT |
| LIMITING DEVICES ARE USUALLY ONLY APPROVED FOR USE ON |
| THE REGULATOR WHEN INSTALLED INDOORS PER THE |
| MANUFACTURER AND ARE NOT APPROVED FOR OUTDOORS. THE |
| REGULATORS ON THIS SYSTEM ARE SHOWN OUTDOORS. |
| 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS FOR THE TANKLESS WATER HEATERS AND THE |
| GAS RANGE. THE WATER HEATERS AND RANGE SHALL BE LISTED |
| AND LABELED. 2014 FBC-FUEL GAS SEC.301.3. 2ND REQUEST. |
| |
| I SUGGEST MAKING AN APPOINTMENT WITH THIS REVIEWER TO |
| REVIEW THE COMMENTS PRIOR TO RESUBMITTING THE PLANS. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |