Plan Review Notes
Plan Review Notes For Permit 17080485
Permit Number 17080485
Review Stop G
Sequence Number 2
Notes
Date Text
2017-08-25 12:10:421) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MP
 REGULATORS.NOTHING HAS BEEN SUBMITTED. 2ND REQUEST.
 2) SHOW THE DISTANCE FROM EACH MP REGULATOR TO THE MOST
 REMOTE OUTLET IN THE BRANCH LINE PER THE 2014FBC-FUEL
 GAS SEC. 402.4.1, 2014 FBCR SEC. G 2413.3. THIS IS FOR
 THE LOW PRESSURE SIDE OF EACH MP REGULATOR.2ND REQUEST.
 3) SUBMIT THE CORRECT CORRESPONDING EHD NUMBER FOR THE
 CSST PIPE SIZES. THERE ARE INCORRECT EHD SIZES NOTED ON
 THE GAS RISER FOR THE CORRESPONDING PIPE SIZES.. COMPLY
 WITH THE SIZING TABLE(S) IN THE 2014 FBC-FUEL GAS OR
 THE WARDFLEX GAS SIZING TABLE.SUBMIT TWO COPIES OF THE
 WARDFLEX PIPE SIZING TABLE FOR REVIEW FOR THE SIZING OF
 THE CSST. WPB AMEND. TO FBC SEC. 107.3.5.3. 2ND REQUEST
 4) I HAVE ADDED THE TOTAL BTU LOAD SEVERAL TIMES AND I
 HAVE CALCULATED 2,229,000 BTU'S. PLEASE CHECK YOUR BTU
 AND REVISE.
 5) THE GAS RISER SHOWS A 1/2 INCH GALVANIZED NEAR THE
 GAS RANGE SUPPLYING A 1 INCH CSST LINE THAT SUPPLIES
 TWO FIREPLACES. IS THIS CORRECT? THE 1/2 INCH
 GALVANIZED LINE IS UNDERSIZED. CLARIFY.
 6) SHOW THE TYPE OF PIPING AND LENGTH FOR THE 1/2 INCH
 DROP TO THE BBQ AND ALSO THE 3/4 INCH RISER TO THE BBQ.
 7) THE 3/4 CSST BRANCH LINE SUPPLYING THE FIREPLACE IN
 THE FIRST FLOOR LOGGIA AND THE SECOND FLOOR MASTER
 TERRACE IS UNDERSIZED.COMPLY WITH 2014 FBC-FUEL GAS
 CHAPTER 4.
 8) SHOW THE LENGTH OF SECTION OF PIPING FOR ALL RISERS
 TO THE 2ND FLOOR. WPB AMEND. TO FBC SEC. 107.3.5.3.
 9) SHT. P103 NOTE ON PLANS REFERS TO THE GAS REGULATORS
 BEING EQUIPPED WITH A LEAK LIMITING DEVICE. VENT
 LIMITING DEVICES ARE USUALLY ONLY APPROVED FOR USE ON
 THE REGULATOR WHEN INSTALLED INDOORS PER THE
 MANUFACTURER AND ARE NOT APPROVED FOR OUTDOORS. THE
 REGULATORS ON THIS SYSTEM ARE SHOWN OUTDOORS.
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE TANKLESS WATER HEATERS AND THE
 GAS RANGE. THE WATER HEATERS AND RANGE SHALL BE LISTED
 AND LABELED. 2014 FBC-FUEL GAS SEC.301.3. 2ND REQUEST.
  
 I SUGGEST MAKING AN APPOINTMENT WITH THIS REVIEWER TO
 REVIEW THE COMMENTS PRIOR TO RESUBMITTING THE PLANS.
  