Plan Review Notes
Plan Review Notes For Permit 17080475
Permit Number 17080475
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-06 14:25:322014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080475
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 8C
 CONT: SUFFOLK
 TEL: 561-407-496-3168 ED HANRATTY
 E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS
 E-MAIL ADDRESS REQUIREMENTS,
 WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN
 RECORD.
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: THURSDAY SEPT. 14/2017 / FRI. OCT. 06/ 2017
 ACTION: DENIED
  
 1A) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE KITCHEN BOTH OF THESE DOORS AS SHOWN
 IN THE OPEN POSITION MEASURE 2.50 FT. FAIR HOUSING
 REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014 FBC-
 ACCESSIBILITY/ FAIR HOUSING SECTION 100.205.(C)(2)(2).
  
 1B) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE KITCHEN, PLEASE PROVIDE WHAT TYPE OF
 HANDLES WILL BE INSTALLED ON THE POCKET DOORS CANNOT BE
 FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE
 THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1C) SHEET 126-15-A2-90-8C SHOWS (4 POCKET DOORS LEADING
 INTO THE MASTER BEDROOM CLOSETS & HIS & HERS MASTER
 BATH ALL OF THESE DOORS AS SHOWN IN THE OPEN POSITION
 MEASURE 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF
 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING
 SECTION 100.205.(C)(2)(2).
  
 1B) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE MASTER BEDROOM CLOSETS, PLEASE PROVIDE
 WHAT TYPE OF HANDLES WILL BE INSTALLED ON THE POCKET
 DOORS CANNOT BE FULLY RECESSED HARDWARE HAS TO BE
 ACCESSIBLE FOR PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205(C)(2)(2).FIGURE 1( C ).
  
 1E) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO BEDROOM 2 & BEDROOM 3, PLEASE PROVIDE WHAT
 TYPE OF HANDLES WILL BE INSTALLED ON THE POCKET DOORS
 CANNOT BE FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE
 FOR PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1F) SHEET 126-15-A2-90-8C SHOWS (4 POCKET DOORS LEADING
 INTO THE MASTER BEDROOM CLOSETS & HIS & HERS MASTER
 BATH ALL OF THESE DOORS AS SHOWN IN THE OPEN POSITION
 MEASURE 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF
 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING
 SECTION 100.205.(C)(2)(2).
  
 1G) PLEASE BE AWARE ALL OF THE EXTERIOR SLIDING GLASS
 DOORS WILL NEED TO MEET THE 32 INCHES CLEAR AND THE
 HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE
 LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 2) SHEET 242-_15-A6-66-8C FLOOR FINISHES. BLDG TYPE:
 TYPE I/ TYPE II FLOOR INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR
 PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF
 THERE IS A DROP CEILING WITH OR WITHOUT INSULATION:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56B, A6.13B &
 A7.55B AS CUSTOM UNIT SUPPLEMENTAL INDEX AND ADDED
 REFERENCE NOTES, BUT THESE SHEETS ARE NOT PART OF THE
 PLAN SET SUBMITTED? THEN WHY ARE THESE SHEETS LISTED IN
 THE INDEX FOR THIS UNIT? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2017-10-02 15:17:50W. P. B. REVISION: 17080125 CORRECTED NOTES!
 W. P. B. PERMIT: 15111020 NOT: 15050292/ FOUNDATION
 PERMIT
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9B
 CONT: SUFFOLK
 TEL: 561-407-496-3168 ED HANRATTY
 E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS
 E-MAIL ADDRESS REQUIREMENTS,
 WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN
 RECORD.
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: MON. OCT. 02/2017
 ACTION: DENIED
  
 1) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U04B &
 U05B) LEADING INTO THE MASTER BATH HIS & HERS. THE
 DOORS AS SHOWN IN THE OPEN POSITION MEASURE 2.50 FT.
 FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014
 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).
  
 1B) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U04B &
 U05B) LEADING INTO THE MASTER BATHROOMS HIS & HER
 BATHROOMS. PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE
 INSTALLED ON THE POCKET DOORS CANNOT BE FULLY RECESSED
 HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE
 LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205(C)(2)(2).FIGURE 1( C ).
  
 1C) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U05W &
 U05V) LEADING INTO BOTH HIS AND HER MASTER CLOSETS. THE
 DOORS AS SHOWN IN THE OPEN POSITION MEASURE 2.50 FT.
 FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014
 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).
  
 1D) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U05W &
 U05V) LEADING INTO BOTH HIS AND HER MASTER CLOSETS. .
 PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE INSTALLED
 ON THE POCKET DOORS CANNOT BE FULLY RECESSED HARDWARE
 HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE LIMITED HAND
 MOBILITY. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205(C)(2)(2).FIGURE 1( C ).
  
 1E) SHEET 126-18-A2-90-9B PLEASE BE AWARE ALL OF THE
 EXTERIOR SLIDING GLASS DOORS WILL NEED TO MEET THE 32
 INCHES CLEAR AND THE HARDWARE HAS TO BE ACCESSIBLE FOR
 PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 2) SHEET 208-18-A6-25-9B FLOOR FINISHES WOOD FLOORS AND
 TILE FLOORS. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2014)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 2D) THE PLAN DOES NOT SAY IF THE WOOD FLOORS ARE GOING
 TO HAVE AN UNDERLAYMENT ONLY. IF THE FLOORS ARE GOING
 TO USE WOOD SLEEPERS AND THEN COMPLIANCE WILL BE
 REQUIRED UNDER 2010 FBC-B:
 805.1.1 SUBFLOOR CONSTRUCTION.
 FLOOR SLEEPERS, BUCKS AND NAILING BLOCKS SHALL NOT BE
 CONSTRUCTED OF COMBUSTIBLE MATERIALS, UNLESS THE SPACE
 BETWEEN THE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY AND
 THE FLOORING IS EITHER SOLIDLY FILLED WITH
 NONCOMBUSTIBLE MATERIALS OR FIREBLOCKED IN ACCORDANCE
 WITH SECTION 718, AND PROVIDED THAT SUCH OPEN SPACES
 SHALL NOT EXTEND UNDER OR THROUGH PERMANENT PARTITIONS
 OR WALLS.
  
 805.1.2 WOOD FINISH FLOORING.
 WOOD FINISH FLOORING IS PERMITTED TO BE ATTACHED
 DIRECTLY TO THE EMBEDDED OR FIREBLOCKED WOOD SLEEPERS
 AND SHALL BE PERMITTED WHERE CEMENTED DIRECTLY TO THE
 TOP SURFACE OF FIRE-RESISTANCE-RATED FLOOR ASSEMBLIES
 OR DIRECTLY TO A WOOD SUBFLOOR ATTACHED TO SLEEPERS AS
 PROVIDED FOR IN SECTION 805.1.1.
  
 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56A, A6.13A &
 A7.55A WITH ADDED REFERENCED NOTES BUT THESE SHEETS ARE
 NOT IN THE PERMIT PACKAGE. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED. SUBMIT IF THEY ARE PART OF THIS
 REVISION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2017-09-14 10:49:282014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080475
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 8C
 CONT: SUFFOLK
 TEL: 561-407-496-3168 ED HANRATTY
 E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS
 E-MAIL ADDRESS REQUIREMENTS,
 WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN
 RECORD.
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: THURSDAY SEPT. 14/2017
 ACTION: DENIED
  
 1A) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE KITCHEN BOTH OF THESE DOORS AS SHOWN
 IN THE OPEN POSITION MEASURE 2.50 FT. FAIR HOUSING
 REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014 FBC-
 ACCESSIBILITY/ FAIR HOUSING SECTION 100.205.(C)(2)(2).
  
 1B) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE KITCHEN, PLEASE PROVIDE WHAT TYPE OF
 HANDLES WILL BE INSTALLED ON THE POCKET DOORS CANNOT BE
 FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE
 THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1C) SHEET 126-15-A2-90-8C SHOWS (4 POCKET DOORS LEADING
 INTO THE MASTER BEDROOM CLOSETS & HIS & HERS MASTER
 BATH ALL OF THESE DOORS AS SHOWN IN THE OPEN POSITION
 MEASURE 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF
 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING
 SECTION 100.205.(C)(2)(2).
  
 1B) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE MASTER BEDROOM CLOSETS, PLEASE PROVIDE
 WHAT TYPE OF HANDLES WILL BE INSTALLED ON THE POCKET
 DOORS CANNOT BE FULLY RECESSED HARDWARE HAS TO BE
 ACCESSIBLE FOR PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205(C)(2)(2).FIGURE 1( C ).
  
 1E) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO BEDROOM 2 & BEDROOM 3, PLEASE PROVIDE WHAT
 TYPE OF HANDLES WILL BE INSTALLED ON THE POCKET DOORS
 CANNOT BE FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE
 FOR PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1F) SHEET 126-15-A2-90-8C SHOWS (4 POCKET DOORS LEADING
 INTO THE MASTER BEDROOM CLOSETS & HIS & HERS MASTER
 BATH ALL OF THESE DOORS AS SHOWN IN THE OPEN POSITION
 MEASURE 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF
 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING
 SECTION 100.205.(C)(2)(2).
  
 1G) PLEASE BE AWARE ALL OF THE EXTERIOR SLIDING GLASS
 DOORS WILL NEED TO MEET THE 32 INCHES CLEAR AND THE
 HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE
 LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 2) SHEET 242-_15-A6-66-8C FLOOR FINISHES. BLDG TYPE:
 TYPE I/ TYPE II FLOOR INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR
 PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF
 THERE IS A DROP CEILING WITH OR WITHOUT INSULATION:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56B, A6.13B &
 A7.55B AS CUSTOM UNIT SUPPLEMENTAL INDEX AND ADDED
 REFERENCE NOTES, BUT THESE SHEETS ARE NOT PART OF THE
 PLAN SET SUBMITTED? THEN WHY ARE THESE SHEETS LISTED IN
 THE INDEX FOR THIS UNIT? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  