Plan Review Notes For Permit 17080304 |
Permit Number |
17080304 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-14 16:03:35 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED | | SEPARATE PERMITS AND DATA SPECIFICATION SHEET | | SUBMITTALS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT | | NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND DATA, | | WIRELESS SYSTEMS, KITCHEN HOODS ETC. A NOTE WILL | | SUFFICE. | | 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | 8.4.2. FBC C405.7.1 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|