Plan Review Notes For Permit 17080255 |
Permit Number |
17080255 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-08 03:05:54 | THE 975XL IS NOT A LEAD FREE DEVICE. BACKFLOW DEVICES | | SHALL BE LEAD FREE PER 2014 FBC-PLUMBING SEC.605.2.1 | | AND THE CITY OF WPB CROSS - CONNECTION CONTROL MANUAL. | | THE SUBMITTED SPECIFICATION SHEET DOES NOT STATE THAT | | THE DEVICE IS LEAD FREE. SUBMIT TWO COPIES OF THE | | MANUFACTURER'S SPECIFICATIONS SHOWING THAT THE DEVICE | | IS LEAD FREE. | | **NOTE** THE 975 XL2 IS A LEAD FREE DEVICE. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|