2018-06-14 18:13:49 | 1ST REVIEW: FBC 2017 6TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. AT LEAST ONE OF THE WORK SINKS SHALL COMPLY WITH FBC |
| ACC 212.3 , 606 |
| |
| 2. WHAT SINK IS THE WATER HEATER DRAIN PAN DISCHARGING |
| INTO PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 3. PROVIDE 2 COPIES OF THE MANUFACTURE SPECIFICATIONS |
| OF THE WET TABLE IN THE VICHY SHOWER AND THE HAIR |
| WASHING CHAIR SINK ONLY ONE WAS PROVIDED ALSO THE |
| SHOWER VALVE. PER WPB AMEND TO FBC 107.2.1 |
| |
| 4. THE HAIR WASH SINK SHALL BE EQUIPPED WITH A VACUUM |
| BREAKER. PER FBC PL 608.2 |
| |
| 5. ALL VALVES SHALL COMPLY WITH NSF 372 LEAD FREE . PER |
| FBC PL 605.2.1 |
| |
| 6. SHT. P-3 DETAIL I THE SHOWER LINER SHALL BE PITCHED |
| TO TH DRAIN. PER FBC PL 417.5.2 |
| |
| 7. THE LAVATORY IN THE BATHROOM SHALL COMPLY WITH |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3.PER FBC PL 416.5 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |