Plan Review Notes
Plan Review Notes For Permit 17080211
Permit Number 17080211
Review Stop M
Sequence Number 1
Notes
Date Text
2017-08-16 10:28:071ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17080211
 8/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE HAIR SALON REQUIRES EXHAUST VENTILATION AT A
 RATE OF 0.60 CFMS PER SQ. FT., AND THE RECIRCULATION OF
 ANY AIR FROM THE SPACE IS PROHIBITED- SEE TABLE 403.3
 AND FOOTNOTE B. PLEASE PROVIDE A SYSTEM THAT MEETS
 COMPLIANCE.
  
 2) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE PLAN
 WITH CORRESPONDING DRAWINGS AND DETAILS. SHOW ALL
 ALTERATIONS TO THE EXISTING HVAC SYSTEMS.
  
 4) THE BUILDING PLANS EXAMINER IS REQUIRING CODE
 COMPLIANT PLANS DONE BY A LICENSED ARCHITECT WHICH WILL
 CLARIFY WHETHER THE PROPOSED PROJECT IS A CHANGE OF
 OCCUPANCY OR CHANGE OF USE FROM THE PREVIOUS OCCUPANCY.
 BASED ON THOSE COMMENTS, THE MECHANICAL REVIEW IS
 STOPPED AT THIS TIME UNTIL NEW PLANS ARE RESUBMITTED
 FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  