Plan Review Notes
Plan Review Notes For Permit 17080211
Permit Number 17080211
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-14 16:17:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLAN LACKS A SIGNIFICANT AMOUNT OF INFORMATION SUCH
 AS OCCUPANCY CLASSIFICATION, LIFE SAFETY PLAN (TRAVEL
 DISTANCES, EXITS, COMMON PATH OF TRAVEL, ETC.),
 OCCUPANT LOAD, COMPLIANCE WITH FBC ACCESSIBILITY. AS A
 BUILDING PLAN WAS NOT PROVIDED, A COMPLETE REVIEW
 CANNOT BE DONE AT THIS TIME. SOME INFORMATION ON THE
 PLAN IS NOT CLEAR.
  
 FOR INSTANCE, GENERAL NOTES STATES THAT OCCUPANCY TYPE
 IS R1, BUT APPLICATION STATES A HAIR SALON IS PROPOSED.
 IS THIS A CHANGE OF OCCUPANCY?
  
 SOME NOTES ARE NOT CLEAR AS TO MEANING; "ALL CONTRACTOR
 TREAD, SHALL PROVIDE THEIR INFORMATION AND SIGN THEIR
 DRAWING."
  
 FBC 107, PROVIDE AN ARCHITECTURAL QUALITY PLAN PREPARED
 BY A LICENSED DESIGN PROFESSIONAL, FS 471, 481. AN
 ELECTRICAL CONTRACTOR DESIGNED THE ELECTRICAL PORTION,
 A PLUMBING CONTRACTOR (PARTIALLY) DESIGNED THE PLUMBING
 PORTION (BUT NO ACCESSIBILITY INFORMATION PROVIDED).
 SOMETHING WHICH IS LABELED "WALL DETAIL DNS" IS ON THE
 PLAN BUT NOT CLEAR WHETHER THE PLUMBING CONTRACTOR OR
 THE ELECTRICAL CONTRACTOR IS DESIGNING THIS WORK.
  
  
  