2017-08-10 16:18:21 | 1) PROVIDE WHAT TYPE OF POOL HEATER WILL BE USED GAS OR |
| ELECTRIC. PROVIDE MANUFACTURE SPECIFICATIONS 2 COPIES |
| ARE REQUIRED |
| 2) IF GAS PLEASE PROVIDE THE FOLLOWING |
| |
| GAS PERMIT APPLICATION REQUIREMENTS |
| |
| |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| G2413. |
| |
| 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE. |
| WPB AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 3. TYPE OF GAS (LP OR NATURAL). |
| |
| 4. BTU LOAD OF EACH APPLIANCE / EQUIPMENT AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS |
| SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 |
| (37) OR 2014 FBC-RES. SEC. G2413. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER |
| OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 |
| FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G |
| 2407. |
| |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| SEC. G2413.2. . |
| |
| 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426. |
| |
| |
| TIM HUNT |
| PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |