Plan Review Notes For Permit 17080183 |
Permit Number |
17080183 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-22 16:13:15 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | IN AN EFFORT TO CONTINUE TO MOVE THIS PLAN FORWARD, | | THIS PLAN IS APPROVED FOR THE DESIGN AND INSTALL OF THE | | STAIRS ONLY. | | | | THERE IS A CONCERN RELATED TO THE GLASS BLOCKS AS | | INFILL. | | | | | | 1) SHEET A 3.10 - THERE ARE INDICATIONS OF GLASS BLOCKS | | AS INFILL TO OPENINGS INA 2 HOUR RATED STAIRWELL. THERE | | ARE NO INDICATIONS THAT THE GLASS BLOCKS SYSTEM SHOWING | | A LISTING/DESIGN STANDARD MEETING THE 2 HOUR WALL. | | | | PLEASE CLARIFY AND PROVIDE LISTED DETAILS PRIOR TO | | INSTALL OF ANY GLASS BLOCK THAT MEET THE RATING | | REQUIREMENTS. | | | | | | 2) PROVIDE RIVISION SHEETS AS NECASSARY. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|