2017-08-14 06:46:57 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | SHEETS E.1.1 THRU E2.2 STATE TO SEE NOTES AND LEGENDS | | ON PAGE E0.1 WHICH IS NOT INCLUDED WITH THESE DRAWINGS. | | | | FIXTURE SCHEDULE OR TYPE TO BE USED IN STAIRWAY AND | | LANDINGS. | | | | MOUNTING HEIGHT OF FIXTURES ON WALLS (MIN. 80") | | | | IS THE LIGHTING ON AN EMMERGENCY CIRCUTI? | | | | BRANCH CIRCUIT NUMBERS AND/OR SOURCE REQUIRED TO BE ON | | PLANS. | | | | PANEL SCHEDULES. | | | | LIFE SAFETY 101 REQUIRES EMERGENCY BACK UP 90 MINUTES | | FOR EGRESS LIGHTING 7.9.2.1. |
|