Plan Review Notes For Permit 17080183 |
Permit Number |
17080183 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-14 15:29:38 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC B 1014.3, REVISE PLAN TO SHOW WORST CASE COMMON | | PATH OF TRAVEL. THIS IS TO BE MEASURED FROM THE | | FARTHEST POINT IN THE SOUTH END UNITS TO THE PROPOSED | | NEW EXIT STAIR (WHICH NOW BECOMES THE FIRST PLACE WHERE | | THE OCCUPANT HAS A CHOICE OF TWO EXITS). | | | | 2. COMPLIANCE WITH FBC 1609 NOT CLEAR. HAS THE 2 HOUR | | EXTERIOR WALL (UL U308) BEEN EVALUATED FOR RESISTANCE | | TO WIND LOADS? I WAS UNABLE TO FIND A DECLARATION OF | | WIND DESIGN CRITERIA. STRUCTURAL PAGES APPEAR TO BE FOR | | THE STAIR ONLY. PLEASE REVISE PLAN TO INCLUDE WIND | | DESIGN CRITERIA OR CLARIFY. | | | | | | |
|