Plan Review Notes
Plan Review Notes For Permit 17080183
Permit Number 17080183
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-14 15:29:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC B 1014.3, REVISE PLAN TO SHOW WORST CASE COMMON
 PATH OF TRAVEL. THIS IS TO BE MEASURED FROM THE
 FARTHEST POINT IN THE SOUTH END UNITS TO THE PROPOSED
 NEW EXIT STAIR (WHICH NOW BECOMES THE FIRST PLACE WHERE
 THE OCCUPANT HAS A CHOICE OF TWO EXITS).
  
 2. COMPLIANCE WITH FBC 1609 NOT CLEAR. HAS THE 2 HOUR
 EXTERIOR WALL (UL U308) BEEN EVALUATED FOR RESISTANCE
 TO WIND LOADS? I WAS UNABLE TO FIND A DECLARATION OF
 WIND DESIGN CRITERIA. STRUCTURAL PAGES APPEAR TO BE FOR
 THE STAIR ONLY. PLEASE REVISE PLAN TO INCLUDE WIND
 DESIGN CRITERIA OR CLARIFY.
  
  
  