Date |
Text |
2017-08-22 13:18:53 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SMOKE ALARM IS MISSING IN MASTER BEDROOM AND THE |
| AREA ADJACENT TO THE MASTER BEDROOM, PROVIDE |
| CORRECITON. FBC RE314.3 |
| 2. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH |
| GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC |
| 210.70(A)(2)(B), FBC RE3903.3 |
| 3. FOR THE AHU, A LUMINAIRE CONTROLLED BY A SWITCH |
| LOCATED AT THE REQUIRED PASSAGEWAY OPENING AND A |
| RECEPTACLE OUTLET SHALL BE INSTALLED AT OR NEAR THE |
| APPLIANCE LOCATION. FBC RE M1305.1.3.1 |
| 4. DINING ROOM LIGHT IS SHOWN ON THE SMALL APPLIANCE |
| CIRCUIT FOR THE DINING AREA, WHICH IS NOT PERMITTED PER |
| CODE. PROVIDE CORRECTION. NEC 210.11(C)(1), |
| 210.52(B)(2); FBC RE3703.2 |
| 5. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7 |
| 6. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC |
| 107.2.1 |
| 7. PROVIDE CORRECTION FOR AFCI NOTE. NOTE CURRENTLY |
| STATES THAT ALL "RECEPTACLES ..... SHALL HAVE AFCI |
| PROTECTION." CODE STATES: "ALL 120-VOLT, SINGLE PHASE, |
| 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| OR ROOMS, SHALL HAVE AFCI PROTECTION". NEC 210.12; FBC |
| RE3902.12 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |