Plan Review Notes
Plan Review Notes For Permit 17080149
Permit Number 17080149
Review Stop G
Sequence Number 1
Notes
Date Text
2017-08-09 13:07:571) SHOW THE BTU LOAD FOR EACH OF THE TIKI TORCHES. THE
 BTU LOAD OF EACH TIKI TORCH SHALL BE ADDED TO THE TOTAL
 LOAD OF THE GAS SYSTEM. 2014 FBC-FUEL GAS SEC. 401.4.
 2) SHOW THE SIZE OF THE EXISTING PIPE TO THE TIKI
 TORCHES TO ENSURE THE EXISTING SYSTEM IS SIZED PROPERLY
 AND TO DETERMINE IF IT HAS THE ADEQUATE CAPACITY FOR
 THE BTU LOAD. 2014 FBC- FUEL GAS SEC.401.4, 401.8.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 NEW APPLIANCES.APPLIANCES SHALL BE LISTED AND LABELED.
 FGC SEC.301.3.
 4) SHOW THE SIZE AND TYPE OF PIPE DOWNSTREAM OF THE
 REGULATOR AT THE TANKLESS WATER HEATERS.
 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE FOR
 THE LOW PRESSURE SYSTEM.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  