Date |
Text |
2018-09-28 10:51:10 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 17080142 |
| 2ND REVIEW: SEPTEMBER 28, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| I CLEARED COMMENT #1 SINCE I LOCATED THE CONVERSION OF |
| NGVD29 TO NAVD88 ON G-3. |
| HOWEVER, THE REMAINING COMMENTS WERE NOT ADDRESSED. |
| THERE WAS NO COMMENT RESPONSE SHEET FOR FIRST REVIEW |
| BUILDING COMMENTS AND ONLY E-SHEETS WERE UPDATED. |
| PLEASE PROVIDE COMMENT RESPONSE SHEETS AND |
| UPDATED/CLOUDED SHEETS AS NEEDED TO ADDRESS THE |
| COMMENTS. |
| |
| |
| |
| 2017-08-22 15:57:40 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17080142 |
| ADD: 1100 N. FLAGLER DR. LIFT STATION # 20 (SANITARY |
| SEWER) |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-801-3659 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. AUGUST 22, 2017 |
| ACTION: DENIED |
| |
| 1) OK. |
| |
| 2) THE 2ND ISSUE OR UNKNOWN IS WHEN THIS LIFT STATION |
| WAS BUILT TO DETERMINE IF IT IS A PRE-FIRM OR POST FIRM |
| STRUCTURE? PLEASE PROVIDE WHEN THIS STRUCTURE WAS |
| BUILT. |
| |
| 3) THE OTHER ISSUE TO DETERMINE TO WHAT EXTENT THIS |
| STRUCTURE HAS TO COMPLY IS WHAT DOLLAR AMOUNT IS THE |
| LIFT STATION, OR ANOTHER WORD HAS THE LIFT STATION HIT |
| THE 50% OF THE STRUCTURE VALUE AND NEED TO MEET THE |
| STANDARDS OF THE CURRENT CODE. |
| |
| 4) SHEET G-2 THE GENERAL NOTES DOES NOT LIST THE DESIGN |
| CRITERIA FOR THIS BUILDING. OCCUPANCY TYPE WOULD BE |
| UTILITY. IN THE SPECS THIS FACILITY IS LISTED AS A |
| FORCE MAIN AND IT WOULD BE ASSUMED TO BE A RISK |
| CATEGORY III STRUCTURE. SEE TABLE 1604.5 OF THE 2014 |
| FBC-B. THE QUESTION IS THIS BUILDING AND OPERATION TO |
| BE CONSIDERED A WASTE WATER TREATMENT FACILITY AND |
| OTHER PUBLIC UTILITY FACILITIES NOT INCLUDED IN RISK |
| CATEGORY IV, THE RISK CATEGORY WOULD BE A III. |
| |
| 5) 2014 FBC-B 1612.4 DESIGN AND CONSTRUCTION. THE |
| DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES |
| LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH |
| HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF |
| ASCE 7 AND WITH ASCE 24. PLEASE REVIEW IN THE ASCE/ SEI |
| 24-05 THE DEFINITION FOR COASTAL A ZONE. |
| COASTAL A ZONE. IN A COASTAL A ZONE, THE PRINCIPLE |
| SOURCES OF FLOODING MUST BE ASTRONOMICAL HIGH TIDES, |
| STORM SURGE, SEICHES OR TSUNAMIS. DURING THE BASE FLOOD |
| CONDITIONS, THE POTENTIAL FOR BREAKING WAVE HEIGHTS |
| SHALL BE GREATER THAN OR EQUAL TO 1.5 FEET. PLEASE |
| REVIEW ASCE/ SEI TABLE 4-1 AND THE REQUIRED HEIGHT |
| ABOVE EITHER THE BASE FLOOD OR THE DFE. ON THE NEW MAPS |
| NOT ADOPTED AS OF THIS REVIEW THE DESIGN FLOOD |
| ELEVATION, THE DESIGN FLOOD, INCLUDING WAVE HEIGHT, |
| RELATIVE TO THE DATUM SPECIFIED ON THE COMMUNITY?S |
| FLOOD HAZARD MAP. THERE ARE 2 HEIGHTS GIVEN WHEN THE |
| MEMBER ORIENTATION RELATIVE TO THE DIRECTION OF THE |
| WAVE APPROACH: |
| PARALLEL BFE + 1 FT. OR DFE WHICHEVER IS HIGHER. |
| PERPENDICULAR BFE + 2 FT. OR DFE, WHICHEVER IS HIGHER. |
| |
| PLEASE NOTE FROM THE CITY OF WEST PALM BEACH SUMMARY OF |
| COASTAL STILLWATER STUDY TABLE 9 FOR THIS SECTION OF |
| THE INTERCOASTAL WATER WAY GIVEN IN NAV88 IS 7.3 FT. |
| |
| IT WOULD APPEAR THAT THE GENERATOR, AND ATTENDANT |
| UTILITIES WILL NEED TO BE ON A RAISED PLATFORM, WITH |
| STAIRS AND GUARDRAIL AROUND THE TOTAL STRUCTURE. THE |
| LIFT STATION ITSELF WOULD REQUIRE DRY FLOOD PROOFING TO |
| A HEIGHT OF BFE + 1 FT. OR DFE WHICHEVER IS HIGHER, SEE |
| ASCE/ SEI 24-05 TABLE 6-1. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |