Plan Review Notes For Permit 17080142 |
Permit Number |
17080142 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-16 10:16:56 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE AIC RATING OF THE SERVICE | | EQUIPMENT, ATS, AND LIFT STATION CONTROL PANEL IS | | ADEQUATE. NEC 110.9, 110.10, 409.110(4) | | 2. PROVIDE AIC RATING OF SERVICE DISCONNECT, ATS, AND | | LIFT STATION CONTROL PANEL. NEC 110.3, 110.9, | | 409.110(4) | | 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|