2017-08-21 13:57:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE, COPIES OR
 OTHER FACSIMILES ARE NOT ACCEPTABLE. CHAPTER 471,
 FLORIDA STATUTES & 61G15-23.003 FLORIDA ADMINISTRATIVE
 CODE
  
 2) THE POOL PERMIT WILL NOT BE ISSUED UNTIL AN
 APPLICATION FOR THE POOL ELECTRIC SUB PERMIT IS
 SUBMITTED. FBC 105.1
  
 3) FBC-R4501.19 FINAL ELECTRICAL AND BARRIER CODE
 INSPECTION SHALL BE COMPLETED PRIOR TO FILLING THE POOL
 WITH WATER.