2017-10-04 17:21:55 | W. P. B. REVISION: 17080125 CORRECTED NOTES! |
| W. P. B. PERMIT: 15111020 NOT: 15050292/ FOUNDATION |
| PERMIT |
| ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9B |
| CONT: SUFFOLK |
| TEL: 561-407-496-3168 ED HANRATTY |
| E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS |
| E-MAIL ADDRESS REQUIREMENTS, |
| WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN |
| RECORD. |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| SUBJECT TO FAIR HOUSING! |
| |
| 1ST REVIEW |
| DATE: MON. OCT. 02/2017 |
| ACTION: DENIED |
| |
| 1) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U04B & |
| U05B) LEADING INTO THE MASTER BATH HIS & HERS. THE |
| DOORS AS SHOWN IN THE OPEN POSITION MEASURE 2.50 FT. |
| FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014 |
| FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| 100.205.(C)(2)(2). |
| |
| 1B) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U04B & |
| U05B) LEADING INTO THE MASTER BATHROOMS HIS & HER |
| BATHROOMS. PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE |
| INSTALLED ON THE POCKET DOORS CANNOT BE FULLY RECESSED |
| HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE |
| LIMITED HAND MOBILITY. |
| 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| 100.205(C)(2)(2).FIGURE 1( C ). |
| |
| 1C) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U05W & |
| U05V) LEADING INTO BOTH HIS AND HER MASTER CLOSETS. THE |
| DOORS AS SHOWN IN THE OPEN POSITION MEASURE 2.50 FT. |
| FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014 |
| FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| 100.205.(C)(2)(2). |
| |
| 1D) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U05W & |
| U05V) LEADING INTO BOTH HIS AND HER MASTER CLOSETS. . |
| PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE INSTALLED |
| ON THE POCKET DOORS CANNOT BE FULLY RECESSED HARDWARE |
| HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE LIMITED HAND |
| MOBILITY. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| 100.205(C)(2)(2).FIGURE 1( C ). |
| |
| 1E) SHEET 126-18-A2-90-9B PLEASE BE AWARE ALL OF THE |
| EXTERIOR SLIDING GLASS DOORS WILL NEED TO MEET THE 32 |
| INCHES CLEAR AND THE HARDWARE HAS TO BE ACCESSIBLE FOR |
| PEOPLE THAT HAVE LIMITED HAND MOBILITY. |
| 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| 100.205.(C)(2)(2).FIGURE 1( C ). |
| |
| 2) SHEET 208-18-A6-25-9B FLOOR FINISHES WOOD FLOORS AND |
| TILE FLOORS. BLDG TYPE: TYPE I/ TYPE II FLOOR |
| INSULATION (FBC-B 2014) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| 2D) THE PLAN DOES NOT SAY IF THE WOOD FLOORS ARE GOING |
| TO HAVE AN UNDERLAYMENT ONLY. IF THE FLOORS ARE GOING |
| TO USE WOOD SLEEPERS AND THEN COMPLIANCE WILL BE |
| REQUIRED UNDER 2010 FBC-B: |
| 805.1.1 SUBFLOOR CONSTRUCTION. |
| FLOOR SLEEPERS, BUCKS AND NAILING BLOCKS SHALL NOT BE |
| CONSTRUCTED OF COMBUSTIBLE MATERIALS, UNLESS THE SPACE |
| BETWEEN THE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY AND |
| THE FLOORING IS EITHER SOLIDLY FILLED WITH |
| NONCOMBUSTIBLE MATERIALS OR FIREBLOCKED IN ACCORDANCE |
| WITH SECTION 718, AND PROVIDED THAT SUCH OPEN SPACES |
| SHALL NOT EXTEND UNDER OR THROUGH PERMANENT PARTITIONS |
| OR WALLS. |
| |
| 805.1.2 WOOD FINISH FLOORING. |
| WOOD FINISH FLOORING IS PERMITTED TO BE ATTACHED |
| DIRECTLY TO THE EMBEDDED OR FIREBLOCKED WOOD SLEEPERS |
| AND SHALL BE PERMITTED WHERE CEMENTED DIRECTLY TO THE |
| TOP SURFACE OF FIRE-RESISTANCE-RATED FLOOR ASSEMBLIES |
| OR DIRECTLY TO A WOOD SUBFLOOR ATTACHED TO SLEEPERS AS |
| PROVIDED FOR IN SECTION 805.1.1. |
| |
| 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56A, A6.13A & |
| A7.55A WITH ADDED REFERENCED NOTES BUT THESE SHEETS ARE |
| NOT IN THE PERMIT PACKAGE. 107.2.1.3 ADDITIONAL |
| INFORMATION REQUIRED. SUBMIT IF THEY ARE PART OF THIS |
| REVISION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
2017-08-29 14:31:49 | W. P. B. REVISION: 17080125 |
| W. P. B. PERMIT: 15111020 NOT: 15050292/ FOUNDATION |
| PERMIT |
| ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9B |
| CONT: SUFFOLK |
| TEL: 561-407-496-3168 ED HANRATTY |
| E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS |
| E-MAIL ADDRESS REQUIREMENTS, |
| WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN |
| RECORD. |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| SUBJECT TO FAIR HOUSING! |
| |
| 1ST REVIEW |
| DATE: TUESDAY AUGUST 29/2017 |
| ACTION: DENIED |
| |
| |
| 1) SHEET 242.17B-A6-68-9A ENLARGED PLAN- DETAIL 1 / |
| BATHROOM # 2 (SPEC. B) INDICATES REINFORCEMENT FOR |
| OPTIONAL WALL MOUNTED SEAT AT 24 INCHES A.F.F. PLEASE |
| PROVIDE IS THE 24 INCHES THE TOP OF BACKING, CENTER |
| LINE OF BACKING AND WHAT IS THE HEIGHT OF THE BACKING. |
| THE FAIR HOUSING CODE REQUIRES BACKING FOR TUBS AND |
| SHOWERS, AND FOR 36 X 36 INCH SHOWERS THE SHOWER STALL |
| SEAT MUST HAVE REINFORCING TO ALLOW FOR THE |
| INSTALLATION OF AN OPTIONAL WALL HUNG SEAT. FAIR |
| HOUSING ALSO USES THE ANSI A117.1 AND FOR SEATS IN |
| SHOWERS SHALL BE 17 INCHES MINIMUM TO 19 INCHES MAXIMUM |
| ABOVE THE BATHROOM. THE BACKING HAS TO BE IN HEIGHT |
| PLACED TO MEET THE HEIGHT REQUIREMENTS FOUND UNDER FAIR |
| HOUSING AND ANSI A117.1. IF THE DESIGNER WISHES TO HAVE |
| BACKING AT A HIGHER HEIGHT FOR A FUTURE SEAT THEY WILL |
| ALSO NEED TO MEET THE REQUIRED BACKING RANGE BY THE |
| CODE. PLEASE ADD THE ADDITIONAL BACKING REQUIRED AND |
| CLARIFY WHAT THE 24 INCHES ABOVE FINISH FLOOR IS |
| RELATIVE TOO. |
| |
| 2) THE NARRATIVE FOR THE ARCHITECTURAL PLANS AGAIN |
| REFERENCES 4 SHEETS NOT FOUND IN THE REVISION SET OF |
| PLANS, A).01C, A2.56A, A6.13A & A7.55A. W. P. B. |
| ADMINISTRATIVE CODE 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |