Plan Review Notes For Permit 17080096 |
Permit Number |
17080096 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-10 15:26:12 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL | | PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS | | PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. SHOW ALL OF | | THE DUCT WORK ON THE PLANS INCLUDING THETRUNK LINE. | | SHOW THE RETURN AIR TO THE AIRHANDLER ON THE PLANS. IN | | ORDER TO PROVIDE CLARITY THE MECHANICAL PLANS SHOW BE | | ON A SEPARATE FLOOR PLAN. | | | | 2) FBC ENERGY CONSERVATION R403.2.1 REQUIRES SUPPLY | | DUCTS IN ATTICS TO HAVE R-8 INSULATION. PLEASE CORRECT | | THE PLANS. | | | | 3) ENERGY COMPLIANCE FORM R405-2014 IS REQUIRED TO HAVE | | THE PREPARER'S NAME AND THE SIGNATURE OF THE | | OWNER/AGENT ON THE FORM. FBC ENERGY CONSERVATION R103 | | | | 4) THE FORM STATES THAT THIS IS WORST CASE. WORST CASE | | IS USED WHEN THE SAME MODEL HOME WILL BE BUILT ON | | DIFFERENT LOTS WITH DIFFERENT ORIENTATIONS. THIS IS NOT | | THE CASE WITH THIS PROJECT. THEREFORE, THIS IS NOT | | WORST CASE AND IS REQUIRED TO SHOW THE ACTUAL | | ORIENTATION OF THE HOME. FBC ENERGY CONSERVATION | | R405.4.2 | | | | |
|