Plan Review Notes For Permit 17080096 |
Permit Number |
17080096 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-07 14:05:07 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED | | BY A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR | | QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1 | | 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC | | 215.5; FBC 107.2.1 | | 3. PROVIDE ACCURATE LOAD CALCULATION FOR RESIDENCE. NEC | | 220; FBC RE3602.3 | | 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC | | RE3706.2, RE3902 | | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|