2017-08-14 09:29:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE EXTERIOR DOOR PRODUCT APPROVAL THAT WAS
 SUBMITTED (FL10537-R2) IS NOT THE ONE THAT IS SPECIFIED
 ON THE PLANS (FL15227-R2). PLEASE CLARIFY. FBC
 107.3.4.1
  
 2) THE REQUIRED COMPONENT AND CLADDING PRESSURES FOR
 THE NEW EXTERIOR DOORS ARE NOT SPECIFIED ON THE PLANS.
 FBC-R301.2.1
  
 3) FBC-R310.1 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 REQUIRED FROM ROOMS USED FOR SLEEPING. THIS IS AN
 EXISTING SINGLE FAMILY DWELLING AND FBC EXISTING
 BUILDING SECTION 704.1 HAS AN EXECPTION THAT ALLOWS A
 MAXIMUM 5 PERCENT REDUCTION IN THE CLEAR OPENING
 DIMENSIONS OF REPLACEMENT WINDOWS AS LONG AS THE
 PORTION OF THE BUILDING IS NOT ALTERED SUCH THAT THE
 BUILDING BECOMES LESS SAFE THAN ITS EXISTING CONDITION
 PER SECTION 701.2. SHOW ON THE PLANS HOW THE NEW
 WINDOWS WILL COMPLY WITH SECTION 701.2 OR HOW THE
 OPENINGS WILL BE ALTERED TO COMPLY WITH FBC-R310.1.