Plan Review Notes For Permit 17080085 |
Permit Number |
17080085 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-07 15:02:08 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED | | BY A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR | | QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1 | | 2. PROVIDE MORE DETAIL FOR PANEL SCHEDULE, INDICATING | | ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE | | FOR THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE | | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, | | 215.5, 408.4; FBC RE3706.2, RE3902 | | 3. WATER HEATER BREAKER SHOULD BE RATED AT 125% OF FULL | | LOAD CURRENT. 30 AMP BREAKER STATED IS TOO LARGE. | | PROVIDE CORRECTION. NEC 422.13, FBC RE4101.4 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|