Plan Review Notes For Permit 17080081 |
Permit Number |
17080081 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2017-11-16 16:13:27 | TALKED TO RODNEY. HE SAID TO APPROVE BUILDING AND | | MECHANICAL REVIEWS WITH PROVISO. HE IS AWARE THAT | | REVISION FEES MAY APPLY AFTER PERMIT IS ISSUED. JG. | | | | MECHANICAL REVIEW APPROVED WITH PROVISO (PROVIDE | | INFORMATION PRIOR TO INSPECTIONS TO AVOID | | CONFLICTS/DELAYS) (PROVIDE 2 COPIES): | | 1- A/C PLAN NEEDS TO SHOW COMPLIANCE WITH THE BALANCED | | RETURN AIR FOR ALL ROOMS REQUIRED BY SEC. M1602.4 | | FBC-RESIDENTIAL, 5TH EDITION (2014). SIZE OF TRANSFER | | DUCT SPECIFIED FOR THE MASTER BEDROOM, STUDY/BEDROOM | | AND BEDROOMS #2 AND #3 IS TOO SMALL. REVISE A/C PLAN AS | | REQUIRED. | | | | 2- EQUIPMENT SIZING CALCULATIONS SHOW A 4 TON A/C UNIT. | | CFM'S SHOWN ON THE A/C PLAN EXCEED THE CAPACITY OF THE | | EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING | | CALCULATIONS. REVISE CFM'S AS REQUIRED. SEC. R103.2 | | FBC-ENERGY CONSERVATION. | | NOTE: COORDINATE INFORMATION WITH PLANS SUBMITTED WITH | | THE EQUIPMENT SIZING CALCULATIONS. | | | | 3- MECHANICAL PLAN M-101 IS MISSING THE CFM'S FOR THE | | DINING ROOM. SEC. R103.2 FBC-ENERGY CONSERVATION. | | | | NOTE: | | WHEN THE AIR HANDLING UNIT IS LOCATED IN THE ATTIC, THE | | SERVICE PANEL NEED TO BE WITHIN 6 FEET OF THE ATTIC | | ACCESS AS REQUIRED BY SEC. R403.2.4 FBC-ENERGY | | CONSERVATION. |
|