2017-11-16 16:13:27TALKED TO RODNEY. HE SAID TO APPROVE BUILDING AND
 MECHANICAL REVIEWS WITH PROVISO. HE IS AWARE THAT
 REVISION FEES MAY APPLY AFTER PERMIT IS ISSUED. JG.
  
 MECHANICAL REVIEW APPROVED WITH PROVISO (PROVIDE
 INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS) (PROVIDE 2 COPIES):
 1- A/C PLAN NEEDS TO SHOW COMPLIANCE WITH THE BALANCED
 RETURN AIR FOR ALL ROOMS REQUIRED BY SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014). SIZE OF TRANSFER
 DUCT SPECIFIED FOR THE MASTER BEDROOM, STUDY/BEDROOM
 AND BEDROOMS #2 AND #3 IS TOO SMALL. REVISE A/C PLAN AS
 REQUIRED.
  
 2- EQUIPMENT SIZING CALCULATIONS SHOW A 4 TON A/C UNIT.
 CFM'S SHOWN ON THE A/C PLAN EXCEED THE CAPACITY OF THE
 EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE CFM'S AS REQUIRED. SEC. R103.2
 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE INFORMATION WITH PLANS SUBMITTED WITH
 THE EQUIPMENT SIZING CALCULATIONS.
  
 3- MECHANICAL PLAN M-101 IS MISSING THE CFM'S FOR THE
 DINING ROOM. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 NOTE:
 WHEN THE AIR HANDLING UNIT IS LOCATED IN THE ATTIC, THE
 SERVICE PANEL NEED TO BE WITHIN 6 FEET OF THE ATTIC
 ACCESS AS REQUIRED BY SEC. R403.2.4 FBC-ENERGY
 CONSERVATION.