Plan Review Notes For Permit 17080081 |
Permit Number |
17080081 |
|
Review Stop |
R |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-11-07 14:25:14 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | FAC 61G20-3.001 FOR: | | A) ROOF TILE ADHESIVE THAT IS LISTED IN THE ROOF TILE | | NOA 16-0314.08 SUBMITTED. NOTE: CLEARLY SPECIFY PADDY | | SIZE TO VERIFY COMPLIANCE WITH THE REQUIRED ATTACHMENT | | RESISTANCE. COORDINATE WITH ROOF TILE NOA SUBMITTED. | | RESPONSE: REPEAT COMMENT. SAME NOA THAT WAS SUBMITTED | | THE FIRST TIME WAS RE-SUBMITTED. RTA-1 ADHESIVE NOA | | 16-0315.03 IS NOT LISTED IN THE CONCRETE TILE NOA | | SUBMITTED. IF CONTRACTOR WANTS TO USE THE RTA-1, THEN | | PROVIDE COMPLETE PACKAGE FOR BUILDING OFFICIAL REVIEW | | AND APPROVAL. CONTACT ME FOR ADDITIONAL INFORMATION. | | | | 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT | | APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: | | ARCHITECT TO PLACE THE REVIEW STAMP ON THE FRONT OF THE | | COVER PAGE NOT ON THE BACK. THIS IS REQUIRED TO | | FACILITATE PROPER SCANNING OF ALL DOCUMENTS. | | |
|