2017-11-07 14:40:58RESIDENTIAL (R3) ADDITION/ALTERATION THIRD MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT PERMIT MAY BE ISSUED AND CONTRACTOR WILL
 BRING REQUIRED INFORMATION PRIOR TO INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. REVISION FEES APPLY.
 CONTRACTOR TO ADVICE IN WRITING IF PROVISO OPTION IS
 PREFERRED AT THIS TIME.
  
  
  
 1- A/C PLAN NEEDS TO SHOW COMPLIANCE WITH THE BALANCED
 RETURN AIR FOR ALL ROOMS REQUIRED BY SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE:
 A) SIZE OF TRANSFER DUCT SPECIFIED FOR THE MASTER
 BEDROOM IS TOO SMALL. SIZE NEEDS TO BE BE BASED ON THE
 TOTAL SUPPLY AIR THAT GOES INTO THE MASTER BEDROOM,
 INCLUDING THE CLOSETS AND BATHROOM. SEE EXCEPTION #3 OF
 SEC. M1602.4 FBC-RESIDENTIAL. NEED AT LEAST 19" DUCT
 SIZE (BASED ON THE SPECIFIED CFM'S) AND HAVING THE DOOR
 WITH AT LEAST AN UNRESTRICTED 1 INCH UNDERCUT. REVISE
 AS REQUIRED. REPEAT COMMENT. REVISED SIZE OF 14"
 DOESN'T COMPLY. NEED AT LEAST 19" DUCT.
  
 B) SIZE OF TRANSFER DUCT SPECIFIED FOR THE
 STUDY/BEDROOM AND BEDROOMS #2 AND #3 IS TOO SMALL. THE
 SIZE OF THE DUCT NEEDS TO BE 1-1/2 TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM AND HAVING THE DOOR WITH AT LEAST AN
 UNRESTRICTED 1 INCH UNDERCUT. SEE EXCEPTION #1 OF SEC.
 M1602.4 FBC-RESIDENTIAL. NEED AT LEAST 10" DUCT SIZE.
 REVISE AS REQUIRED. REPEAT COMMENT. SIZE WAS NOT
 REVISED. NEED AT LEAST 10" DUCT.
  
 C) EQUIPMENT SIZING CALCULATIONS SHOW A 4 TON A/C UNIT.
 CFM'S SHOWN ON THE A/C PLAN EXCEED THE CAPACITY OF THE
 EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE CFM'S AS REQUIRED. SEC. R103.2
 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE INFORMATION WITH PLANS SUBMITTED WITH
 THE EQUIPMENT SIZING CALCULATIONS.
  
 D) MECHANICAL PLAN M-101 IS MISSING THE CFM'S FOR THE
 DINING ROOM. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 NOTE:
 WHEN THE AIR HANDLING UNIT IS LOCATED IN THE ATTIC, THE
 SERVICE PANEL NEED TO BE WITHIN 6 FEET OF THE ATTIC
 ACCESS AS REQUIRED BY SEC. R403.2.4 FBC-ENERGY
 CONSERVATION.
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS...
 *****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS TO RESUBMITTED SET.
 SUBMIT OLD DRAWINGS FOR REFERENCE.
  