2017-08-22 15:22:20 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW | | COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- ALL PLANS NEED THE ORIGINAL SIGNATURE (NOT COPY) OF | | THE ARCHITECT. FAC 61G1-16.003. | | | | 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AS | | REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH | | EDITION (2014). NOTE: MAKE SURE EQUIPMENT LISTED IN THE | | CALCULATIONS MATCH EQUIPMENT SHOWN ON THE A/C PLAN TO | | AVOID CONFLICTS/DELAYS. | | | | 3- A/C PLAN NEEDS TO SHOW COMPLIANCE WITH THE BALANCED | | RETURN AIR FOR ALL ROOMS REQUIRED BY SEC. M1602.4 | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | 4- PROVIDE SPECIFICATIONS FOR THE CLOTHES DRYER | | EXHAUST. SEC. M1502 FBC-RESIDENTIAL. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING | | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS... | | *****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD | | DRAWING. DON'T STAPLE OLD DRAWINGS TO RESUBMITTED SET. | | SUBMIT OLD DRAWINGS FOR REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION. | | (561)805-6712 | | [email protected] |
|