2017-08-17 10:07:24CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. GENERAL ELECTRICAL NOTES, NOTE #10 STATES THAT THE
 MINIMUM WIRE SIZE SHALL BE #12, BUT PANEL SCHEDULE
 SHOWS CIRCUITS FED WITH #14. PROVIDE CORRECTION. FBC
 107.2.1
 2. GENERAL ELECTRICAL NOTES, NOTE #27 STATES THAT "NM"
 SHALL NOT BE USED, BUT NOTE #7 OF ELECTRICAL NOTES
 STATES "ROMEX IS ACCEPTABLE". PROVIDE CORRECTION. FBC
 107.2.1
 3. ELECTRICAL NOTES, NOTE #8 EXPLAINS WHERE AFCI
 PROTECTION SHOULD BE USED. HOWEVER, IT DOES NOT COVER
 ALL AREAS REQUIRED PER CODE: "ALL 120-VOLT, SINGLE
 PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR
 SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION".
 PROVIDE CORRECTION. NEC 210.12; FBC RE3902.12
 4. ELECTRICAL NOTES, NOTE #17 STATES THAT LIGHTING IN
 CLOSETS SHALL COMPLY WITH 410.8. THIS CODE SECTION DOES
 NOT APPLY TO CLOSET LIGHTING. PROVIDE CORRECTION. NEC
 410.16; FBC RE4003.12
 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 6. OUTLETS ARE MISSING IN THE MASTER BEDROOM.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET.
 PROVIDE CORRECTION. NEC 210.52; FBC RE3901.2.1
 7. PLAN SHOWS A CHANDELIER ABOVE THE TUB IN MASTER
 BATH. THE CEILING HEIGHT IS SHOWN AS 10'7". NO PARTS OF
 CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR
 CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. PROVIDE CORRECTION. NEC 410.10(D); FBC
 RE 4003.11
 8. LIGHT ABOVE SHOWER IN POWDER BATH IS SHOWN AS A
 STANDARD RECESS LIGHT. LIGHTING IN BATHTUB OR SHOWER
 AREAS SHALL BE SUITABLE FOR DAMP LOCATIONS. PROVIDE
 CORRECTION. NEC 410.10(D); FBC RE4003.11
 9. PROVIDE GFCI PROTECTED OUTLET ON REAR OF HOUSE. NEC
 210.52(E); FBC RE3901.7
 10. ISLAND RECEPTACLES IN KITCHEN REQUIRED GFCI
 PROTECTION. NEC 210.8; FBC RE3902.6
 11. OUTLET FOR GARAGE DOOR OPENER REQUIRES GFCI
 PROTECTION. NEC 210.8; FBC RE3902.2
 12. SHOW LOCATIONS OF ALL PANELS AND THE SERVICE ON
 PLAN. FBC 107.2.1
 13. SHOW THE MECHANICAL EQUIPMENT ON PLAN, INCLUDING
 THE OUTLET REQUIRED FOR SERVICING OF EQUIPMENT. FBC
 107.2.1, FBC RE3901.12; NEC 210.63
 14. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR POOL AND ALL LOW VOLTAGE SYSTEMS TO
 INCLUDE BUT NOT LIMITED TO FIRE ALARM, CCTV, PHONE AND
 DATA, WIRELESS SYSTEMS, ETC. FBC 105.1
 15. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3 ADDITIONALLY, A 1/0
 WIRE IS SPECIFIED FOR THE GROUNDING ELECTRODE
 CONDUCTOR, WHICH IS NOT TYPICAL FOR THIS SIZE SERVICE,
 ONLY A #4 WIRE IS REQUIRED. NEC 250.66; FBC RE TABLE
 3603.1. RISER SHOWS A #6 EQUIPMENT GROUNDING CONDUCTOR
 (EGC) IN THE CONDUIT BETWEEN THE METER AND THE MAIN
 DISCONNECT. THE EGC IS ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT. PROVIDE CORRECTION. FBC RE3704.6;
 NEC 250.4, 250.6
 16. PANEL SCHEDULE SHOWS #8 ROMEX ON A 50 AMP BREAKER
 FEEDING THE OVEN AND WATER HEATER. #8 ROMEX IS NOT
 RATED FOR 50 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC
 RE3705.4.4
 17. BREAKER FOR WATER HEATER SHOULD BE SIZED AT 125% OF
 LOAD. PROVIDE CORRECTION. NEC 422.13; FBC RE4101.5
 18. THERE IS NO CIRCUIT INCLUDED IN PANEL SCHEDULES FOR
 THE CONDENSING UNIT. ADD TO SCHEDULE AND IDENTIFY WIRE
 AND BREAKER SIZE. ADJUST LOAD CALCULATION IF NECESSARY.
 NEC 215.5, 408.4, 310.15(B)(16); FBC 107.2.1; FBC
 RE3701.2
 19. BREAKER FOR POOL PUMP SHOULD BE GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 680.21(C); FBC RE4203.1.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  