2017-08-21 18:13:59 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| THERE IS A RED TAG FOR DEMOLITION WORK WITHOUT PERMIT. |
| PLEASE GET THE DEMOLITION PERMIT TO CLOSE EXPIRED |
| DEMOLITION PERMIT APPLICATION 16080126. |
| |
| |
| 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- ALL PLANS NEED THE ORIGINAL SIGNATURE (NOT COPY) OF |
| THE ARCHITECT. FAC 61G1-16.003. |
| |
| 3- PROVIDE ENERGY CALCULATIONS. SEC. R101.4.3 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| 4 SETBACK DIMENSIONS SHOWN ON THE ARCHITECTURAL SITE |
| PLAN ON SHEET A-101 DON'T MATCH DIMENSIONS SHOWN ON THE |
| SURVEY. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 5- NEED TO PROVIDE EGRESS WINDOWS FOR NEW STUDY/BEDROOM |
| SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. |
| R310 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 6- BEDROOM #2 EGRESS WINDOWS. PROVIDE MANUFACTURER'S |
| CUT SHEETS SHOWING THAT THE SPECIFIED WINDOW SIZE |
| COMPLIES WITH ALL THE EGRESS REQUIREMENTS OF SEC. R310 |
| FBC-RESIDENTIAL. |
| |
| 7- CLARIFY ROOFING MATERIAL TO BE INSTALLED. PROPOSED |
| WALL SECTION ON SHEET A-202 SPECIFIES METAL ROOFING , |
| WHILE EXTERIOR ELEVATIONS SPECIFY BARREL TILE ROOF. |
| REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 8- PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING |
| TO THE MAIN HOUSE. NEED TO SPECIFY SELF CLOSING DEVICE |
| AS REQUIRED BY SEC. R302.5.1 FBC-RESIDENTIAL. |
| NOTE: REVISE CODE SECTIONS CITED ON THE GARAGE |
| SEPARATION NOTES ON SHEET A-202. SEE SEC. R302.5 AND |
| R302.6 FBC-RESIDENTIAL FOR CORRECT CODE SECTION AND |
| REVISE AS REQUIRED. |
| |
| 9- INFORMATION SHOWN ON THE INSULATION TABLE ON SHEET |
| A-202 DOESN'T MATCH INFORMATION SHOWN ON THE WALL |
| SECTION ON SAME SHEET. REVISE AS REQUIRED TO MATCH. SEE |
| WALL INSULATION R-VALUE. ALSO, THE THICKNESS OF R-30 |
| FIBERGLASS CEILING INSULATION IS 9-1/2" +/- NOT 6.5". |
| REVISE AS REQUIRED. SEC. R103.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| 10- PROVIDE DETAIL/SPECS FOR INSULATION BETWEEN THE NEW |
| GARAGE AND DINING A/C AREA. SEC. R103.2 FBC-ENERGY |
| CONSERVATION. |
| |
| 11- SPECIFY ATTIC ACCESS LOCATION AND SIZE SHOWING |
| COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| |
| 12- WIND LOAD INFORMATION ON SHEET S-201: |
| A) REVISE THE WIND LOAD SPEED. THE WIND LOAD IS 170 MPH |
| ULTIMATE WIND LOAD NOT 160MPH. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| B) COMPONENTS AND CLADDING DESIGN PRESSURES ARE BASED |
| ON A TRIBUTARY AREA OF 20S.F. THE EFFECTIVE TRIBUTARY |
| AREA NEEDS TO BE THE ACTUAL TRIBUTARY AREA OR USE THE |
| LOWEST TRIBUTARY AREA. SEE NOTE "C" OF TABLE R301.2(2) |
| FBC-RESIDENTIAL. AND REVISE AS REQUIRED. COORDINATE |
| DESIGN PRESSURES WITH DOOR AND WINDOW SCHEDULE ON SHEET |
| A-401. SPECIFY THE DESIGN PRESSURES FOR THE OVERHEAD |
| GARAGE DOOR. |
| |
| C) GRAVITY LOADING. SPECIFY THE ATTIC LIVE LOAD AS |
| REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. NOTE: TAKE |
| INTO CONSIDERATION NOTES "B" AND "G" AND IF THE ATTIC |
| IS SERVED WITH FIXED STAIRS. |
| |
| 13- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THE |
| OVERHEAD GARAGE DOOR STRUCTURAL BUCK DETAIL. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| |
| 14- SPECIFY CARBON MONOXIDE ALARMS BY THE |
| BEDROOM/SLEEPING ROOMS IN THE REQUIRED LOCATIONS |
| REQUIRED BY SEC. R15 FBC-RESIDENTIAL. |
| |
| 15- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING |
| METHOD AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. |
| IF SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN ROOF |
| TILE ADHESIVE PRODUCT APPROVAL IS REQUIRED. |
| |
| 16- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) ROOF COVERING AS SPECIFIED ON PLANS. COORDINATE WITH |
| ITEM #7 ABOVE. |
| |
| B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGN OF |
| RECORD. NOTE: SEE ROOFING PRODUCT APPROVAL FOR LISTED |
| ADHESIVES. |
| |
| C) SLIDING GLASS DOORS SHOWING THE SIZES SPECIFIED ON |
| PLANS. NOTE: DRAWINGS SUBMITTED ARE NOT LEGIBLE. THEY |
| ARE TOO SMALL. PLEASE PRINT DRAWINGS ON THE LONGEST |
| SIDE OF THE SHEET (PRINT THEM IN LANDSCAPE ORIENTATION |
| TO USE FULL SHEET). |
| |
| D) ENTRY DOOR WITH SIDELITE AND TRANSOM AS SHOWN ON |
| PLANS. |
| |
| E) OVERHEAD GARAGE DOOR. NOTE: DRAWINGS SUBMITTED ARE |
| NOT LEGIBLE. THEY ARE TOO SMALL. PLEASE PRINT DRAWINGS |
| ON THE LONGEST SIDE OF THE SHEET (PRINT THEM IN |
| LANDSCAPE ORIENTATION TO USE FULL SHEET). |
| |
| F) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. NOTE: |
| DRAWINGS SUBMITTED ARE NOT LEGIBLE. THEY ARE TOO SMALL. |
| PLEASE PRINT DRAWINGS ON THE LONGEST SIDE OF THE SHEET |
| (PRINT THEM IN LANDSCAPE ORIENTATION TO USE FULL |
| SHEET). |
| |
| G) HURRICANE SHUTTERS. SINGLE HUNG PRODUCT APPROVAL |
| FL14911.21 SUBMITTED IS FOR NON-IMPACT WINDOWS. ALL |
| WINDOWS AND DOORS WITH GLAZING NEED HURRICANE IMPACT |
| PROTECTION. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| |
| H) WINDOW MULLIONS. AND, CLEARLY SPECIFY MULLION SIZE |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| |
| I) FIXED WINDOWS AS SPECIFIED ON PLANS. |
| |
| J) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS |
| AND ALL DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR OR DESIGNER OF RECORD TO LIST THE FLORIDA |
| PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| CONNECTOR. |
| |
| 17- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS |
| PRIOR TO SUBMITTAL AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| 18- PROVIDE SPECIFICATIONS FOR THE CORNER STEEL COLUMN |
| LOCATED IN THE MATER BATHROOM BY THE FREE STANDING BATH |
| TUB. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 19- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL THE DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. REVISE VALUATION TO INCLUDE ALL WORK AND |
| DESIGN PROFESSIONAL FEES. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS... |
| *****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS TO RESUBMITTED SET. |
| SUBMIT OLD DRAWINGS FOR REFERENCE. |
| |