2017-09-27 12:14:42 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| COMMENT FROM FIRST REVEW: |
| |
| 1. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING |
| TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED |
| VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE |
| UNDERLAYMENT PROPOSED TO [email protected]. IF THE |
| MANUFACTURER HAS ALREADY PROVIDED THE REQUIRED TEST |
| REPORTS DIRECTLY TO US, TEST REPORTS DO NOT NEED TO BE |
| SUBMITTED WHEN RESUBMITTING. |
| |
| PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |
| 2ND REVIEW - SPEC SHEET FOR PROFLEX MSC 90 WAS |
| SUBMITTED. A LETTER DATED 8/27/14 FROM PROFLEX TO ME |
| STATED THAT THEY DO NOT HAVE THE STC/IIC TESTS WITHOUT |
| A DROPPED CEILING. |
| |
| WE DO HAVE THE TEST REPORTS FOR PROFLEX SUPERSIM 90 ON |
| FILE. |
| |
| NEW COMMENT: |
| |
| 2. VALUE IS TOO LOW FOR THE WORK PROPOSED, FBC 109. ALL |
| PLANS RELATED TO THE PROPOSED RENOVATION ARE TO BE |
| SUBMITTED WITH THIS SUBMITTAL AND THE VALUE OF ALL |
| IMPROVEMENTS ARE TO BE INCLUDED, INCLUDING |
| SUBCONTRACTORS AND MATERIAL PROVIDED BY OTHERS. |
| |
| 3. A LETTER STATES THAT "A CHASE IS BEING RAISED". THE |
| PROPOSED WORK IS NOT SHOWN ON THE PLANS, NO DETAIL |
| PROVIDED. FBC 107, PLANS ARE TO SHOW SCOPE AND NATURE |
| OF PROPOSED WORK. THE INDIVIDUAL TAKING RESPONSIBILITY |
| FOR THE DESIGN IS TO SIGN THE PLAN. DEPENDING ON THE |
| QUALITY OF THE RESUBMITTAL, IT IS POSSIBLE THAT A |
| DESIGN PROFESSIONAL WILL BE REQUIRED TO PROVIDE A PLAN. |
| |