Plan Review Notes
Plan Review Notes For Permit 17080040
Permit Number 17080040
Review Stop B
Sequence Number 2
Notes
Date Text
2017-09-27 12:14:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENT FROM FIRST REVEW:
  
 1. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected]. IF THE
 MANUFACTURER HAS ALREADY PROVIDED THE REQUIRED TEST
 REPORTS DIRECTLY TO US, TEST REPORTS DO NOT NEED TO BE
 SUBMITTED WHEN RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 2ND REVIEW - SPEC SHEET FOR PROFLEX MSC 90 WAS
 SUBMITTED. A LETTER DATED 8/27/14 FROM PROFLEX TO ME
 STATED THAT THEY DO NOT HAVE THE STC/IIC TESTS WITHOUT
 A DROPPED CEILING.
  
 WE DO HAVE THE TEST REPORTS FOR PROFLEX SUPERSIM 90 ON
 FILE.
  
 NEW COMMENT:
  
 2. VALUE IS TOO LOW FOR THE WORK PROPOSED, FBC 109. ALL
 PLANS RELATED TO THE PROPOSED RENOVATION ARE TO BE
 SUBMITTED WITH THIS SUBMITTAL AND THE VALUE OF ALL
 IMPROVEMENTS ARE TO BE INCLUDED, INCLUDING
 SUBCONTRACTORS AND MATERIAL PROVIDED BY OTHERS.
  
 3. A LETTER STATES THAT "A CHASE IS BEING RAISED". THE
 PROPOSED WORK IS NOT SHOWN ON THE PLANS, NO DETAIL
 PROVIDED. FBC 107, PLANS ARE TO SHOW SCOPE AND NATURE
 OF PROPOSED WORK. THE INDIVIDUAL TAKING RESPONSIBILITY
 FOR THE DESIGN IS TO SIGN THE PLAN. DEPENDING ON THE
 QUALITY OF THE RESUBMITTAL, IT IS POSSIBLE THAT A
 DESIGN PROFESSIONAL WILL BE REQUIRED TO PROVIDE A PLAN.
  