2017-08-30 08:55:16 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| ENERGY CONSERVATION CODES |
| PERMIT #17071273 |
| 8/30/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. |
| PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED CFMS OF OUTDOOR AIR. |
| |
| 2) BASED ON THE BUILDING PLAN REVIEW COMMENT #1 |
| INDICATING THE PROPOSED PROJECT MAY BE A CHANGE OF |
| OCCUPANCY, PLEASE REVIEW SECTION C101.4.6 FBC-14 ENERGY |
| CONSERVATION AND PROVIDE A COMPLIANCE SUBMITTAL- SEE |
| SECTION C401.2 FOR COMPLIANCE PATH INFORMATION. |
| |
| 3) SHEETS M1.1 & M1.2: PLEASE PROVIDE AC EQUIPMENT |
| SCHEDULES LISTING THE MAKES AND MODELS OF THE EXISTING |
| SYSTEMS, AND THE SYSTEM CAPACITIES- COOLING AND HEATING |
| BTUHS AND TOTAL SUPPLY CFMS. |
| |
| 4) M1.1 & M1.2: SHOW THE RETURN AIR SYSTEMS. PLEASE |
| NOTE THAT SMOKE DETECTORS MAY BE REQUIRED WHERE SYTEMS |
| EXCEED 2000 CFMS IN CAPACITY- SECTION 606.2.1. |
| |
| 5) M1.1: PLAN NOTE #3 INDICATES FIRE DAMPERS AT DUCT |
| PENETRATIONS HOWEVER NO DUCTS ARE SHOWN AT THESE |
| LOCATIONS. IT APPEARS THAT THE THESE ARE TRANSFER |
| GRILLS. PLEASE REVIEW SECTION 601.2 WHICH PROHIBITS AIR |
| TO BE TRANSFERRED TO A CORRIDOR AS A MEANS OF RETURNING |
| AIR. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |