Plan Review Notes
Plan Review Notes For Permit 17071273
Permit Number 17071273
Review Stop M
Sequence Number 1
Notes
Date Text
2017-08-30 08:55:161ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17071273
 8/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) BASED ON THE BUILDING PLAN REVIEW COMMENT #1
 INDICATING THE PROPOSED PROJECT MAY BE A CHANGE OF
 OCCUPANCY, PLEASE REVIEW SECTION C101.4.6 FBC-14 ENERGY
 CONSERVATION AND PROVIDE A COMPLIANCE SUBMITTAL- SEE
 SECTION C401.2 FOR COMPLIANCE PATH INFORMATION.
  
 3) SHEETS M1.1 & M1.2: PLEASE PROVIDE AC EQUIPMENT
 SCHEDULES LISTING THE MAKES AND MODELS OF THE EXISTING
 SYSTEMS, AND THE SYSTEM CAPACITIES- COOLING AND HEATING
 BTUHS AND TOTAL SUPPLY CFMS.
  
 4) M1.1 & M1.2: SHOW THE RETURN AIR SYSTEMS. PLEASE
 NOTE THAT SMOKE DETECTORS MAY BE REQUIRED WHERE SYTEMS
 EXCEED 2000 CFMS IN CAPACITY- SECTION 606.2.1.
  
 5) M1.1: PLAN NOTE #3 INDICATES FIRE DAMPERS AT DUCT
 PENETRATIONS HOWEVER NO DUCTS ARE SHOWN AT THESE
 LOCATIONS. IT APPEARS THAT THE THESE ARE TRANSFER
 GRILLS. PLEASE REVIEW SECTION 601.2 WHICH PROHIBITS AIR
 TO BE TRANSFERRED TO A CORRIDOR AS A MEANS OF RETURNING
 AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  