Plan Review Notes
Plan Review Notes For Permit 17071242
Permit Number 17071242
Review Stop P
Sequence Number 1
Notes
Date Text
2017-08-03 16:02:061) PLEASE INDICATE THE MODEL OF THE PVB ON THE
 SPECIFICATIONS ONE IS NOT LEAD FREE AS REQUIRED BY THE
 CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL
 AND ONLY THE NON-LEAD FREE DEVICE IS NOTED ON THE
 SPECIFICATION SHEET AS BEING ON THE USC LIST OF
 APPROVED DEVICES.
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
 3) THE LEAD FREE MODEL OF THE PVB IS NOT LISTED ALL
 BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF SOUTHERN
 CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES.
 4) PLEASE INDICATE ON APPLICATION WHERE THESE DEVISES
 WILL BE INSTALLED. PER WPB AMEND TO FBC 107.2.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved