Plan Review Notes For Permit 17071238 |
Permit Number |
17071238 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-02 10:20:04 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NEED RISER DIAGRAM | | | | NOTES STATE THAT THE MAIN IS 200A AND THE PANEL IS | | 125A? | | | | SMOKE ALARMS WILL BE REQUIRED SEE FBC RESIDENTIAL R314. | | | | REPLACEMENT OUTLETS SHALL BE TAMPER RESISTANT AND | | PROTECTED BY AN ARC FAULT CIRCUIT INTERRUPTOR. PER | | 406.4 (D)(1), AND (D)(5) OF THE 2011 NEC |
|