2017-07-31 05:24:051) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE
 DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION. THE SUBMITTED
 DOCUMENTS ARE SERVICE, REPLACEMENT PARTS AND
 MAINTENANCE SHEETS AND DO NOT SHOW THE REQUIRED
 INFORMATION.
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. THE
 SUBMITTED DOCUMENTS DO NOT REFLECT THE SPECIFIC DEVICE
 THAT IS BEING INSTALLED AND THAT IT IS LEAD FREE.
 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
 THE SUBMITTED DOCUMENTS DO NOT SHOW THE DEVICE IS ON
 USC'S LIST.
 4) CLEARLY INDICATE IF ANY OF THESE DEVICES ARE BEING
 INSTALLED ON A FIRE PROTECTION SYSTEM. YOU MUST BE
 LICENSED AS A FIRE PROTECTION CONTRACTOR "I", "II" OR
 "V" IN ORDER TO PERFFORM ANY WWORK ON A WATER BASED
 FIRE PROTECTION SYSTEM PER FL. STATUTE 633.102.
 5) INDICATE THE SIZE OF THE BACKFFLOWS TO BE INSTALLED
 ON ALL DOCUMENTS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED
 IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH
 PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO
 ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE
 DEVICE.
  
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL CAN BE FOUND AT :
 HTTP://WPB.ORG/UTILITIES/BACKFLOW
  
 UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS:
 WWW.USC.EDU/DEPT/FCCCHR
  