Date |
Text |
2017-07-31 05:22:40 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| SPECIFICATIONS FOR THE BACKFLOW PREVENTER. THE MAKE, |
| MODEL AND SIZE OF THE DEVICE SHALL BE NOTED IN THE |
| DESCRIPTION OF WORK SECTION ON THE PERMIT APPLICATION. |
| THE SUBMITTED DOCUMENTS ARE SERVICE, REPLACEMENT PARTS |
| AND MAINTENANCE SHEETS AND DO NOT SHOW THE REQUIRED |
| INFORMATION. |
| 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. THE |
| SUBMITTED DOCUMENTS DO NOT REFLECT THE SPECIFIC DEVICE |
| THAT IS BEING INSTALLED AND THAT IT IS LEAD FREE. |
| 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF |
| SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES. |
| THE SUBMITTED DOCUMENTS DO NOT SHOW THE DEVICE IS ON |
| USC'S LIST. |
| 4) CLEARLY INDICATE IF ANY OF THESE DEVICES ARE BEING |
| INSTALLED ON A FIRE PROTECTION SYSTEM. YOU MUST BE |
| LICENSED AS A FIRE PROTECTION CONTRACTOR "I", "II" OR |
| "V" IN ORDER TO PERFFORM ANY WWORK ON A WATER BASED |
| FIRE PROTECTION SYSTEM PER FL. STATUTE 633.102. |
| 5) INDICATE THE SIZE OF THE BACKFFLOWS TO BE INSTALLED |
| ON ALL DOCUMENTS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 6) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED |
| IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND |
| CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES |
| DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH |
| PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO |
| ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE |
| DEVICE. |
| |
| THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL |
| MANUAL CAN BE FOUND AT : |
| HTTP://WPB.ORG/UTILITIES/BACKFLOW |
| |
| UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS: |
| WWW.USC.EDU/DEPT/FCCCHR |
| |
| QUESTIONS REGARDING PERMITTING REQUIREMENTS MAY BE |
| DIRECTED TO: |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| CITY OF WEST PALM BEACH |
| 561-805-6692 |
| [email protected] |
| |