Plan Review Notes
Plan Review Notes For Permit 17071094
Permit Number 17071094
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-03 15:53:34BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE LEGIBLE PLAN.
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 2. PROVIDE DETAIL OF POOL BARRIER GATE.
 R4501.17.1.8
 ACCESS GATES, WHEN PROVIDED, SHALL BE SELF-CLOSING AND
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS
 R4501.17.1.1 THROUGH R4501.17.1.7 AND SHALL BE EQUIPPED
 WITH A SELF-LATCHING LOCKING DEVICE LOCATED ON THE POOL
 SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS LOCATED
 NO LESS THAN 54 INCHES (1372 MM) FROM THE BOTTOM OF THE
 GATE, THE DEVICE RELEASE MECHANISM MAY BE LOCATED ON
 EITHER SIDE OF THE GATE AND SO PLACED THAT IT CANNOT BE
 REACHED BY A YOUNG CHILD OVER THE TOP OR THROUGH ANY
 OPENING OR GAP FROM THE OUTSIDE. GATES THAT PROVIDE
 ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM
 THE POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING
 GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457
 MM) OF THE RELEASE MECHANISM.
  
 3. DESIGNER TO PRINT NAME AND SIGN PLAN.
 THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE SUBMITTED PLANS
 AND SUPPORTING DOCUMENTS PER FBC 107.