Plan Review Notes For Permit 17071073 |
Permit Number |
17071073 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-22 08:37:11 | 1) THE REVISED PLUMBING PLANS APPEAR TO HAVE COPIED | | ENGINEERS SEALS AND SIGNATURES. PLEASE PROVIDE ORIGINAL | | SIGNED AND SEALED DRAWINGS IN ACCORDANCE WITH SECTION | | 61G15-23.001, 23.002 FAC. | | 2) SUBMIT A NARRATIVE THAT ITEMIZES ALL CHANGES MADE TO | | EACH PLUMBING PLAN SHEET, AND PROVIDE CLOUDS AND | | SYMBOLS TO HIGHLIGHT THOSE CHANGES ON THE PLANS.WPB | | AMEND. TO FBC SEC. 107.2.1. | | 3) SHT. A-104A - DETAIL #9 - SHOW THE SIZE DIMENSIONS | | OF THE SCUPPER. THE SCUPPER SHALL BE LOCATED PER FBC | | SEC. 1504.4.2.1. | | 4) SHT. A-402A - DETAIL #9 - THE SHOWER CONTROLS FOR | | THE HANDICAP ACCESSIBLE SHOWER SHALL COMPLY WITH THE | | 2014 FBC-ACCESSIBILITY SEC. 608.5.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|