2017-08-22 08:37:111) THE REVISED PLUMBING PLANS APPEAR TO HAVE COPIED
 ENGINEERS SEALS AND SIGNATURES. PLEASE PROVIDE ORIGINAL
 SIGNED AND SEALED DRAWINGS IN ACCORDANCE WITH SECTION
 61G15-23.001, 23.002 FAC.
 2) SUBMIT A NARRATIVE THAT ITEMIZES ALL CHANGES MADE TO
 EACH PLUMBING PLAN SHEET, AND PROVIDE CLOUDS AND
 SYMBOLS TO HIGHLIGHT THOSE CHANGES ON THE PLANS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A-104A - DETAIL #9 - SHOW THE SIZE DIMENSIONS
 OF THE SCUPPER. THE SCUPPER SHALL BE LOCATED PER FBC
 SEC. 1504.4.2.1.
 4) SHT. A-402A - DETAIL #9 - THE SHOWER CONTROLS FOR
 THE HANDICAP ACCESSIBLE SHOWER SHALL COMPLY WITH THE
 2014 FBC-ACCESSIBILITY SEC. 608.5.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW