Plan Review Notes
Plan Review Notes For Permit 17071073
Permit Number 17071073
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-07 15:09:57BUILDING PLAN REVIEW
 W. P. B. REVISION: 17071073
 W. P. B. PERMIT: 16071078
 ADD: 1718 PARKER AVENUE/ FIRE STATION # 4
 CONT: HEDRICK BROTHERS
 TEL: 561-662-8049
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. AUGUST 07/ 2017
 ACTION: DENIED
  
 1) THE CHANGE/ REVISION FROM CBS (CONCRETE, BLOCK &
 STEEL) CONSTRUCTION TO TILT WALL CONSTRUCTION WILL
 REQUIRE A RESIDENT INSPECTOR ON SITE THRU THE ROOF
 FRAMING AND DOOR DECK INSPECTIONS.
 THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR
 PROGRAM. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION/ TILT WALL
 CONSTRUCTION.
  
 1A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT. FORMS E-MAILED TO:
 [email protected] AT 08/07/2017 / 03:09 PM.
 [email protected] 08/31/17 / 08:15 AM.
  
 1B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1D) COMPLIED. NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS
 ARE REQUIRED.
  
 1E) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2) SHEET LS-101MAKES REFERENCES TO TABLE 601 AND NO
 FIRE RATING OF FLOOR SYSTEMS. THIS IS TRUE BUT THERE IS
 NO REFERENCE TO THE REQUIREMENT OF FIRE RATED FLOOR
 ASSEMBIES FOR R2 SLEEPING ROOMS UNDER SECTION 420.3
 HORIZONTAL SEPARATION AND THE REQUIRED IN FBC-B 711.3
 AND TABLE 707.3.10.
 3) SHEET A-100 PLAN REVISION HAS A NOTE THAT THE 2ND
 FLOOR ASSEMBLY HAS BEEN CHANGED TO AN 8 INCH HOLLOW
 CORE SLAB PLEASE PROVIDE THE FIRE RATING OF THE 2ND
 FLOOR 8 INCH HOLLOW CORE SLAB ASSEMBLY IN ACCORDANCE
 WITH 420.3 HORIZONTAL SEPARATION AND THE REQUIRED IN
 FBC-B 711.3 AND TABLE 707.3.10. PLEASE NOTE SHEET S-000
 INDICATES THIS FLOOR SYSTEM IS ACTUALLY 6 INCH CONCRETE
 HOLLOW CORE PLANK WITH 2 INCHES OF TOPPING.
 DISCREPANCY IN PLANS.
  
 4A) SHEET A-101A, HAS A NEW NOTE ABOUT WHEEL CHAIR LIFT
 REQUIREMENTS. PLEASE SPECIFY IF THE INTENT IS TO USE A
 LULA, LIMITED USE/ LIMITED APPLICATION ELEVATOR
 CLASSIFIED BY ASTM A17.1 OR IF THE SPECIFICATION IS FOR
 A PLATFORM LIFT CLASSIFIED UNDER ASTM E A18.1. PLEASE
 NOTE IF THE INTENT IS TO USE A PLATFORM LIFT UNDER ASTM
 E A18.1 IN NEW CONSTRUCTION IT IS VERY LIMITED USES,
 THE 2014 FBC-ACCESSIBILITY CODE SECTION 296.7 HAS ONLY
 (5) EXCEPTIONS FOR NEW CONSTRUCTION. EXCEPTION 3 ALLOWS
 FOR NOT ALLOWED FOR PUBLIC USE BUT THE EXCEPTION ALSO
 STATES TO BE OCCUPIED BY NOT MORE THAN 5 OCCUPANTS.
  
 4B) THE CHANGE SHOWING A 4 INCH RECESS FOR LIFT MAYBE
 CHANGED WHEN THE MANUFACTURERS SHOP DRAWINGS ARE
 SUBMITTED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. LULA, LIMITED USE/ LIMITED APPLICATION
 ELEVATOR CLASSIFIED BY ASTM A17.1.
  
 5) SHEET A-102A HAS A NOTE THAT MOST CMU WALLS HAVE
 BEEN REPLACED. THIS SHEET SHOWS THE DORM ROOM CORRIDOR
 WALLS AND WALLS ADJACENT TO ANOTHER DORM WITH A WALL
 TAG TYPE 2 WALL. THE LEGEND IDENTIFIES THE WALLS AS A 1
 HOUR FIRE RATED WALL. SHEET -500 DOES NOT SHOW THE WALL
 TYPE 2 AS FIRE RATED. SEE SECTION 420.2 OF THE 2014
 FBC-B AND THE REQUIREMENT FOR FIRE PARTITIONS IN
 COMPLIANCE WITH 708.3.
  
 6) SHEET A-102 THE DOOR IDENTIFICATION TAGS ARE TURNED
 OFF ON THIS SHEET. THE 1ST FLOOR DOOR TAGS ARE TURNED
 ON. SHEET A-600 THE DOOR SCHEDULE FOR THE DOOR ROOM
 DOORS # 34, 35, 39-43 ALL ARE MISSING THE FIRE RATING
 OF THE DOORS, SEE ISSUED SET OF PLANS SHOW A DOOR
 CLOSER AND 45 MINUTE FIRE RATING, FBC-B TABLE 716.5.
 NOTE THIS IS NOT SHOWN AS A REVISION!!!
  
 7) SHEET A-600 1ST FLOOR DOORS MISSING FIRE RATINGS,
 05, 05A STAIR # 1, DOOR # 17 MISSING LOCATION, CAPTAINS
 OFFICE MISSING FIRE RATING AND REDUCED TO 2 FT.- 10
 INCHES, REQUIRES 3 FEET FBC-B 1008.1.1, STAIR # 2 AND
 2A MISSING CLOSER AND FIRE RATINGS TABLE 716.5. DOOR 19
 MISSING ALL INFORMATION, LEADS INTO A I HR. FIRE RATED
 SHAFT, CLOSER 1ST FLOOR AND 2ND FLOOR TABLE 716.5 .
 NOTE THIS IS NOT SHOWN AS A REVISION!!!
  
 8) SHEET A-103 SHOWS A NOTE FOR FIRE RATED UPPER
 DRYWALL CEILING THROUGH DORMS 1-5 BUT THERE IS NO NOTE
 FOR THE FIRE RATING OF THE (2) CAPTAINS DORM ROOM.
 WHERE DOES THE WALL FIRE RATINGS STOP IN THE CAPTAINS
 DORM WHY NO RATING OF THE CEILING IN THIS DORM?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. WALL RATINGS
 TO THE ROOF STRUCTURE NO REQUIRED CEILING RATING, IF
 THE DRYWALL CEILING IS RATED THEN A WALL DAMPER WOULD
 BE REQUIRED.
  
 9) A-104 HAS INCLUDED MORE SPECS FOR THE CARLISLE ROOF
 SYSTEM, PLEASE PRODUCE THE PRODUCT APPROVAL FOR THE
 LIGHTWEIGHT CONCRETE AND CARLISLE ROOF AT THE SAME
 TIME. BOTH SUBMITTALS WILL NEED TO AGREE ON THE VENTING
 FOR THE LIGHTWEIGHT CONCRETE. THE LIGHTWEIGHT CONCRETE
 AS WELL AS THE ROOFING MANUFACTURER WILL HAVE OPTIONS
 FOR VENTING OF THE LIGHTWEIGHT CONCRETE. PLEASE
 IDENTIFY WHICH OPTION.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TERM "LEGAL" OR ?OR? ITS EQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 10) SHEET A-104A DETAIL # 9 AN OVERFLOW SCUPPER NEEDS
 TO HAVE A MINIMUM AND MAXIMUM THE BOTTOM OF THE SCUPPER
 CAN BE LOCATED ABOVE THE FINISH ROOF, SHOW COMPLIANCE
 WITH 2014 FBC-B 1503.4.2.1.
  
 11) TILT WALL PANEL WALL SYSTEM PLANS PN-1-PN19 ARE
 FROM A SPECIALTY ENGINEER. THE ENGINEER OF RECORD DOES
 NOT HAVE THEIR SHOP DRAWING STAMP OF APPROVAL ON THESE
 PLANS. 61G15-30.003 ENGINEERING DOCUMENT
 CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 12A) ONLY 2 SETS OF TILT WALL CALCULATIONS SUBMITTED 3
 ORIGINAL SIGNED AND SEALED REQUIRED AND TO BE REVIEWED
 BY THE ENGINEER OF RECORD FOR THE PROJECT BEFORE BEING
 SUBMITTED TO THE BUILDING DEPARTMENT. DELEGATED
 ENGINEERING. 61G15-30.003 ENGINEERING DOCUMENT
 CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 12B) THE 2 SETS OF TILT-UP PANEL CALCULATIONS
 COVERSHEET IS SIGNED AND SEALED, PLEASE NOTE THE
 COVERPAGE DOES NOT LIST HOW MANY PAGES ARE COVERED
 UNDER THIS REPORT. 61G15-23.002(2) FL. ADMIN. CODE. A
 COVER SHEET OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET
  
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  