2017-08-07 15:09:57 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17071073 |
| W. P. B. PERMIT: 16071078 |
| ADD: 1718 PARKER AVENUE/ FIRE STATION # 4 |
| CONT: HEDRICK BROTHERS |
| TEL: 561-662-8049 |
| E-MAIL: [email protected] |
| |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: MON. AUGUST 07/ 2017 |
| ACTION: DENIED |
| |
| 1) THE CHANGE/ REVISION FROM CBS (CONCRETE, BLOCK & |
| STEEL) CONSTRUCTION TO TILT WALL CONSTRUCTION WILL |
| REQUIRE A RESIDENT INSPECTOR ON SITE THRU THE ROOF |
| FRAMING AND DOOR DECK INSPECTIONS. |
| THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR |
| PROGRAM. 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| METHODS OF CONSTRUCTION/ TILT WALL |
| CONSTRUCTION. |
| |
| 1A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| DEPARTMENT. FORMS E-MAILED TO: |
| [email protected] AT 08/07/2017 / 03:09 PM. |
| [email protected] 08/31/17 / 08:15 AM. |
| |
| 1B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| |
| 1C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| |
| 1D) COMPLIED. NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS |
| ARE REQUIRED. |
| |
| 1E) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 2) SHEET LS-101MAKES REFERENCES TO TABLE 601 AND NO |
| FIRE RATING OF FLOOR SYSTEMS. THIS IS TRUE BUT THERE IS |
| NO REFERENCE TO THE REQUIREMENT OF FIRE RATED FLOOR |
| ASSEMBIES FOR R2 SLEEPING ROOMS UNDER SECTION 420.3 |
| HORIZONTAL SEPARATION AND THE REQUIRED IN FBC-B 711.3 |
| AND TABLE 707.3.10. |
| 3) SHEET A-100 PLAN REVISION HAS A NOTE THAT THE 2ND |
| FLOOR ASSEMBLY HAS BEEN CHANGED TO AN 8 INCH HOLLOW |
| CORE SLAB PLEASE PROVIDE THE FIRE RATING OF THE 2ND |
| FLOOR 8 INCH HOLLOW CORE SLAB ASSEMBLY IN ACCORDANCE |
| WITH 420.3 HORIZONTAL SEPARATION AND THE REQUIRED IN |
| FBC-B 711.3 AND TABLE 707.3.10. PLEASE NOTE SHEET S-000 |
| INDICATES THIS FLOOR SYSTEM IS ACTUALLY 6 INCH CONCRETE |
| HOLLOW CORE PLANK WITH 2 INCHES OF TOPPING. |
| DISCREPANCY IN PLANS. |
| |
| 4A) SHEET A-101A, HAS A NEW NOTE ABOUT WHEEL CHAIR LIFT |
| REQUIREMENTS. PLEASE SPECIFY IF THE INTENT IS TO USE A |
| LULA, LIMITED USE/ LIMITED APPLICATION ELEVATOR |
| CLASSIFIED BY ASTM A17.1 OR IF THE SPECIFICATION IS FOR |
| A PLATFORM LIFT CLASSIFIED UNDER ASTM E A18.1. PLEASE |
| NOTE IF THE INTENT IS TO USE A PLATFORM LIFT UNDER ASTM |
| E A18.1 IN NEW CONSTRUCTION IT IS VERY LIMITED USES, |
| THE 2014 FBC-ACCESSIBILITY CODE SECTION 296.7 HAS ONLY |
| (5) EXCEPTIONS FOR NEW CONSTRUCTION. EXCEPTION 3 ALLOWS |
| FOR NOT ALLOWED FOR PUBLIC USE BUT THE EXCEPTION ALSO |
| STATES TO BE OCCUPIED BY NOT MORE THAN 5 OCCUPANTS. |
| |
| 4B) THE CHANGE SHOWING A 4 INCH RECESS FOR LIFT MAYBE |
| CHANGED WHEN THE MANUFACTURERS SHOP DRAWINGS ARE |
| SUBMITTED. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. LULA, LIMITED USE/ LIMITED APPLICATION |
| ELEVATOR CLASSIFIED BY ASTM A17.1. |
| |
| 5) SHEET A-102A HAS A NOTE THAT MOST CMU WALLS HAVE |
| BEEN REPLACED. THIS SHEET SHOWS THE DORM ROOM CORRIDOR |
| WALLS AND WALLS ADJACENT TO ANOTHER DORM WITH A WALL |
| TAG TYPE 2 WALL. THE LEGEND IDENTIFIES THE WALLS AS A 1 |
| HOUR FIRE RATED WALL. SHEET -500 DOES NOT SHOW THE WALL |
| TYPE 2 AS FIRE RATED. SEE SECTION 420.2 OF THE 2014 |
| FBC-B AND THE REQUIREMENT FOR FIRE PARTITIONS IN |
| COMPLIANCE WITH 708.3. |
| |
| 6) SHEET A-102 THE DOOR IDENTIFICATION TAGS ARE TURNED |
| OFF ON THIS SHEET. THE 1ST FLOOR DOOR TAGS ARE TURNED |
| ON. SHEET A-600 THE DOOR SCHEDULE FOR THE DOOR ROOM |
| DOORS # 34, 35, 39-43 ALL ARE MISSING THE FIRE RATING |
| OF THE DOORS, SEE ISSUED SET OF PLANS SHOW A DOOR |
| CLOSER AND 45 MINUTE FIRE RATING, FBC-B TABLE 716.5. |
| NOTE THIS IS NOT SHOWN AS A REVISION!!! |
| |
| 7) SHEET A-600 1ST FLOOR DOORS MISSING FIRE RATINGS, |
| 05, 05A STAIR # 1, DOOR # 17 MISSING LOCATION, CAPTAINS |
| OFFICE MISSING FIRE RATING AND REDUCED TO 2 FT.- 10 |
| INCHES, REQUIRES 3 FEET FBC-B 1008.1.1, STAIR # 2 AND |
| 2A MISSING CLOSER AND FIRE RATINGS TABLE 716.5. DOOR 19 |
| MISSING ALL INFORMATION, LEADS INTO A I HR. FIRE RATED |
| SHAFT, CLOSER 1ST FLOOR AND 2ND FLOOR TABLE 716.5 . |
| NOTE THIS IS NOT SHOWN AS A REVISION!!! |
| |
| 8) SHEET A-103 SHOWS A NOTE FOR FIRE RATED UPPER |
| DRYWALL CEILING THROUGH DORMS 1-5 BUT THERE IS NO NOTE |
| FOR THE FIRE RATING OF THE (2) CAPTAINS DORM ROOM. |
| WHERE DOES THE WALL FIRE RATINGS STOP IN THE CAPTAINS |
| DORM WHY NO RATING OF THE CEILING IN THIS DORM? |
| 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. WALL RATINGS |
| TO THE ROOF STRUCTURE NO REQUIRED CEILING RATING, IF |
| THE DRYWALL CEILING IS RATED THEN A WALL DAMPER WOULD |
| BE REQUIRED. |
| |
| 9) A-104 HAS INCLUDED MORE SPECS FOR THE CARLISLE ROOF |
| SYSTEM, PLEASE PRODUCE THE PRODUCT APPROVAL FOR THE |
| LIGHTWEIGHT CONCRETE AND CARLISLE ROOF AT THE SAME |
| TIME. BOTH SUBMITTALS WILL NEED TO AGREE ON THE VENTING |
| FOR THE LIGHTWEIGHT CONCRETE. THE LIGHTWEIGHT CONCRETE |
| AS WELL AS THE ROOFING MANUFACTURER WILL HAVE OPTIONS |
| FOR VENTING OF THE LIGHTWEIGHT CONCRETE. PLEASE |
| IDENTIFY WHICH OPTION. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| TERM "LEGAL" OR ?OR? ITS EQUIVALENT BE USED AS A |
| SUBSTITUTE FOR SPECIFIC INFORMATION. |
| |
| 10) SHEET A-104A DETAIL # 9 AN OVERFLOW SCUPPER NEEDS |
| TO HAVE A MINIMUM AND MAXIMUM THE BOTTOM OF THE SCUPPER |
| CAN BE LOCATED ABOVE THE FINISH ROOF, SHOW COMPLIANCE |
| WITH 2014 FBC-B 1503.4.2.1. |
| |
| 11) TILT WALL PANEL WALL SYSTEM PLANS PN-1-PN19 ARE |
| FROM A SPECIALTY ENGINEER. THE ENGINEER OF RECORD DOES |
| NOT HAVE THEIR SHOP DRAWING STAMP OF APPROVAL ON THESE |
| PLANS. 61G15-30.003 ENGINEERING DOCUMENT |
| CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED |
| ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| |
| 12A) ONLY 2 SETS OF TILT WALL CALCULATIONS SUBMITTED 3 |
| ORIGINAL SIGNED AND SEALED REQUIRED AND TO BE REVIEWED |
| BY THE ENGINEER OF RECORD FOR THE PROJECT BEFORE BEING |
| SUBMITTED TO THE BUILDING DEPARTMENT. DELEGATED |
| ENGINEERING. 61G15-30.003 ENGINEERING DOCUMENT |
| CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED |
| ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| |
| 12B) THE 2 SETS OF TILT-UP PANEL CALCULATIONS |
| COVERSHEET IS SIGNED AND SEALED, PLEASE NOTE THE |
| COVERPAGE DOES NOT LIST HOW MANY PAGES ARE COVERED |
| UNDER THIS REPORT. 61G15-23.002(2) FL. ADMIN. CODE. A |
| COVER SHEET OR INDEX SHEET FOR ENGINEERING |
| SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| PREPARATION OF EACH SECTION OF THE ENGINEERING |
| SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| THE COVER SHEET OR INDEX SHEET |
| |
| |
| 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |