2017-08-14 13:22:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17071018
 8/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) VERIFY THAT THE TEMPERATURE DIFFERENTIAL OF THE
 MAKEUP AIR FOR THE HOOD EXHAUST SYSTEMS AND THE AIR IN
 THE CONDITIONED SPACE DOES NOT EXCEED 10 DEGREES, OR
 PROVIDE TEMPERED MAKE UP AIR- SECTION 508.1.1.
  
 2) SUBMITTALS REQUIRED TO BE REVIEWED AND APPROVED BY
 THE EOR: 1) UL LISTED GREASE EXHAUST DUCT. 2)
 MIAMI-DADE NOA'S FOR THE FANS.
  
 3) SHEET #7 & 8: AS NOTED IN THE CALCULATIONS 2273 CFMS
 OF O/A FROM THE AC SYSTEMS WILL BE PROVIDED AS MAKEUP
 AIR FOR THE HOODS. PLEASE INDICATE WHICH AC SYSTEMS
 WIIL BE PROVIDING THE AIR TO EACH EXHAUST HOOD- SEE THE
 MAIN PERMIT PLANS FOR THE PROJECT.
  
 4) SHEET #9: PROVIDE WIND LOAD ENGINEERING AND DESIGN
 CRITERIA FOR CONSTRUCTION AND ATTACHMENT OF THE WALL
 BRACKETS, AND ATTACHMENT OF THE FANS TO THE BRACKETS-
 SECTION 301.15.
  
 5) SHEET #9: THE DRAWING INDICATES THAT THE POSITION OF
 THE EXHAUST FAN OPENING WILL ALLOW FOR WATER TO INTRUDE
 INTO IT. PLEASE PROVIDE A MEANS OF PROTECTION.
  