Plan Review Notes For Permit 17071018 |
Permit Number |
17071018 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-14 13:22:48 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17071018 | | 8/14/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) VERIFY THAT THE TEMPERATURE DIFFERENTIAL OF THE | | MAKEUP AIR FOR THE HOOD EXHAUST SYSTEMS AND THE AIR IN | | THE CONDITIONED SPACE DOES NOT EXCEED 10 DEGREES, OR | | PROVIDE TEMPERED MAKE UP AIR- SECTION 508.1.1. | | | | 2) SUBMITTALS REQUIRED TO BE REVIEWED AND APPROVED BY | | THE EOR: 1) UL LISTED GREASE EXHAUST DUCT. 2) | | MIAMI-DADE NOA'S FOR THE FANS. | | | | 3) SHEET #7 & 8: AS NOTED IN THE CALCULATIONS 2273 CFMS | | OF O/A FROM THE AC SYSTEMS WILL BE PROVIDED AS MAKEUP | | AIR FOR THE HOODS. PLEASE INDICATE WHICH AC SYSTEMS | | WIIL BE PROVIDING THE AIR TO EACH EXHAUST HOOD- SEE THE | | MAIN PERMIT PLANS FOR THE PROJECT. | | | | 4) SHEET #9: PROVIDE WIND LOAD ENGINEERING AND DESIGN | | CRITERIA FOR CONSTRUCTION AND ATTACHMENT OF THE WALL | | BRACKETS, AND ATTACHMENT OF THE FANS TO THE BRACKETS- | | SECTION 301.15. | | | | 5) SHEET #9: THE DRAWING INDICATES THAT THE POSITION OF | | THE EXHAUST FAN OPENING WILL ALLOW FOR WATER TO INTRUDE | | INTO IT. PLEASE PROVIDE A MEANS OF PROTECTION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|