Date |
Text |
2017-10-30 06:49:48 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17071006 |
| ADD: 4375 EASLEY DR. / EAST CENTRAL WATER RECLAMATION |
| FACILITY |
| PROCESS WATER SYSTEM PROJECT |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-835-7406 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: MON. OCT.30/2017 |
| ACTION: BUILDING PROVISO |
| |
| 1) BUILDING PROVISO/ DEFERRED SUBMITTAL/ SHOP DRAWINGS |
| & SIGNED & SEALED CALCULATIONS.. SHEET S-PWS-10 SHOWS A |
| SECTION 1 SHOWS SECONDARY EFFLUENT TRANSFER PUMP |
| STATION. NOTE 2 OF THIS PAGE INDICATES SEE DRILL |
| LOCATION AND ELEVATION ON M DRAWINGS. M-PWS-10 SHOWS A |
| SECTION B GIVING THE CENTERLINE OF THE PIPE AND |
| ASSOCIATED HOLE AT AN ELEVATION 4.25. FINISH GRADE IS |
| AT 25.00. PLEASE PROVIDE |
| WHAT REQUIREMENTS ARE TO BE PUT IN PLACE FOR SAME |
| GUARDING THE SURROUNDING STRUCTURES AS WELL AS THE |
| DEWATERING REQUIRED TO GET A STABLE, DRY & WORKABLE |
| GROUND AT ELEVATION 4.25 FT. ELEVATION. THIS SAME |
| ELEVATION IS GOING TO BE REQUIRED TO BE A STABLE DRY |
| GROUND FOR THE EXTENSION OF THE 48 INCH EFFLUENT PIPE. |
| |
| 2A) BUILDING PROVISO/ DEFERRED SUBMITTAL/ SHOP DRAWINGS |
| & SIGNED & SEALED CALCULATIONS. |
| FBC-B 1804.1 EXCAVATION NEAR FOUNDATIONS. EXCAVATION |
| FOR ANY PURPOSE SHALL NOT REMOVE LATERAL SUPPORT FROM |
| ANY FOUNDATION WITHOUT FIRST UNDERPINNING OR PROTECTING |
| THE FOUNDATION AGAINST SETTLEMENT OR LATERAL |
| TRANSLATION. |
| |
| 2B) BUILDING PROVISO/ DEFERRED SUBMITTAL/ SHOP DRAWINGS |
| & SIGNED & SEALED CALCULATIONS. FBC-B 1805.1.3 |
| GROUND-WATER CONTROL. THE DESIGN OF THE SYSTEM TO LOWER |
| THE GROUND-WATER TABLE SHALL BE BASED ON ACCEPTED |
| PRINCIPLES OF ENGINEERING THAT SHALL CONSIDER, BUT NOT |
| NECESSARILY BE LIMITED TO, PERMEABILITY OF THE SOIL, |
| RATE AT WHICH WATER ENTERS THE DRAINAGE SYSTEM, RATED |
| CAPACITY OF PUMPS, HEAD AGAINST WHICH PUMPS ARE TO |
| OPERATE AND THE RATED CAPACITY OF THE DISPOSAL AREA OF |
| THE SYSTEM. |
| |
| 2C) BUILDING PROVISO/ DEFERRED SUBMITTAL/ SHOP DRAWINGS |
| & SIGNED & SEALED CALCULATIONS. THE PLANS ARE SILENT AS |
| TO HOW THE GROUND IS TO BE HELD BACK WHEN THE WORK AREA |
| WILL BE BELOW 4.25 FT. NGVD. WILL THE USE OF DRIVEN |
| SHEET PILE BE USED IN THIS TYPE OF APPLICATION, TO HELP |
| HOLD BACK WATER AND SOILS FROM LATERAL MOVEMENT, IF SO |
| HOW MUCH TOE IS TO BE REQUIRED TO MAINTAIN SOILS |
| SATIABILITY? 1810.3.1.4 DRIVEN PILES. DRIVEN PILES |
| SHALL BE DESIGNED AND MANUFACTURED IN ACCORDANCE WITH |
| ACCEPTED ENGINEERING PRACTICE TO RESIST ALL STRESSES |
| INDUCED BY HANDLING, DRIVING AND SERVICE LOADS. |
| |
| 2D) BUILDING PROVISO/ DEFERRED SUBMITTAL/ SHOP |
| DRAWINGS. THE ISSUE WITH THE AMOUNT OF EARTH TO BE |
| REMOVED, THE LOCATION OF THE SURCHARGE IN RELATION TO |
| THE EXCAVATION MAYBE A SAFETY CONCERN. FBC-B 3304.1.2 |
| SURCHARGE. NO FILL OR OTHER SURCHARGE LOADS SHALL BE |
| PLACED ADJACENT TO ANY BUILDING OR STRUCTURE UNLESS |
| SUCH BUILDING OR STRUCTURE IS CAPABLE OF WITHSTANDING |
| THE ADDITIONAL LOADS CAUSED BY THE FILL OR SURCHARGE. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |