Plan Review Notes
Plan Review Notes For Permit 17071006
Permit Number 17071006
Review Stop M
Sequence Number 1
Notes
Date Text
2017-08-25 12:33:171ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17071006
 8/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M=PWS-80: MECHANICAL VENTILATION IS REQUIRED
 FOR THE CHEMICAL STORAGE VAULTS- SECTION 414.3 FBC-14
 BUILDING, AND SECTION 502.9.2 FBC-14 MECHANICAL.
  
 2) M-PWS-34: PROVIDE WIND LOAD ENGINEERING FOR
 ANCHORING AND TIE DOWN OF THE HYDROPNEUMATIC TANK, THE
 AIR COMPRESSOR, AND THE PUMPS- SECTION 301.15.
  