Plan Review Notes For Permit 17071006 |
Permit Number |
17071006 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-25 12:33:17 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17071006 | | 8/25/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M=PWS-80: MECHANICAL VENTILATION IS REQUIRED | | FOR THE CHEMICAL STORAGE VAULTS- SECTION 414.3 FBC-14 | | BUILDING, AND SECTION 502.9.2 FBC-14 MECHANICAL. | | | | 2) M-PWS-34: PROVIDE WIND LOAD ENGINEERING FOR | | ANCHORING AND TIE DOWN OF THE HYDROPNEUMATIC TANK, THE | | AIR COMPRESSOR, AND THE PUMPS- SECTION 301.15. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|